ERROR CODES
AND DIAGNOSTICS
UNILINK HOST
ADAPTER 6–2
USER MANUAL
000E
An uneven number of bytes was received from the secondary
.
0010
Lost Data Carrier Detect (DCD) from the TIW
A
Y I interface port(s).
0011
Lost Clear T
o Send (CTS) from the TIW
A
Y I interface port(s).
0084 The command processor found an unrecognized command code in the
command
string. This also indicates that the command code is not valid
for the currently configured operating mode. If you receive this error
after issuing one of the Extended HIU or NM commands, you can
assume
that the adapter was reset and needs to be reconfigured.
0085 An invalid field was received with the command code. Check the
command
syntax in Chapter 5.
0086 The length of the command frame received from the host was too long
for
the specified command code.
0087 The
length of the command frame received from the host was too
short.
The minimum length for an NITP protocol frame is 11 bytes. The
minimum
length for a BDLC protocol frame is 9 bytes.
0088 The
secondary device addressed
in the command string is not connected
to the TIWAY I network. Recheck the address in the command string
and the addresses of the secondary devices. Then, issue a CONNECT
SECONDARY
command or enable a macro that was previously defined
to
connect that secondary
.
0089 The
colon that
begins an NITP message frame was missing. Correct the
frame
and retransmit it.
008B The
character count field value did not match the number of characters
received. This could be caused by an error in the software driver. In
either case, your applications software should retry the message at
least
three times. If this same error returns all three times, check for an
error
in your software driver
.
008C The checksum calculated by the adapter did not match the
Error–Checking Code or the Block Checksum field value. Retry the
message
at least three times. If this same error returns all three times,
check
for an error in your software driver
.