ERROR CODES
AND DIAGNOSTICS
UNILINK HOST
ADAPTER6–13
USER MANUAL
6.4.4 External
I/O Loopback T
est
There
is a special diagnostic test for the Input/Output
Points. This test is active
when Positions 9 and 10 of Dipswitch 2 are up. To run this test, perform the
following
steps.
1. Install a 20.0 to 30.0 VDC power supply to the output power terminal
(#3)
shown in Figure 6–5.
2. Using a 22 AWG wire, connect the input point terminal (#1) to the
output
point terminal (#5).
3. Using
another 22 A
WG wire, connect the input point return
(#2) to the
output
point return (#4).
4. Install
the loopback connectors provided with the adapter to Port 3
and
Port
4.
5.
Apply power to the adapter
.
6.
Set Positions 9 and 10 of Dipswitch 2 up.
7.
Press the reset switch.
Pin
1
– Input
2 – Input Return
3 – Power
4 – Output Return
5 – Output
I
NR
T
N
D
C
+
R
T
N
O
U
T
12
345
Figure 6–5 External I/O Loopback Test Connections
If
the External I/O loopback test fails, the pattern shown in Figure 6–4 will be
displayed
on the LEDs. Check the connections shown in Figure 6–5 and retest.
If
the test continues to fail, return the unit for repair
.