Instruction Manual

B.2 Connectors

 

 

 

B.2.1 Fire Relay Connector

 

 

 

 

 

 

 

 

 

(J2) Fire Relay

Description

 

 

 

Pin 1 (Left Most) & Pin 2

Normally Open Side of Relay

 

 

 

Pin 3 & Pin 4 (Middle)

Common or Center Side of Relay

 

 

 

Pin 5 & Pin 6 (Right Most)

Normally Closed Side of Relay

 

 

B.2.2 Verify and Aux. Fault Connector

 

 

 

 

 

 

 

 

(J3) Verify/Aux.

Description

 

Pin 1 (Left Most) & Pin 2

Verify Relay Common Side of Relay

 

 

Pin 3 & Pin 4

Verify Relay NO or NC Side of Relay

 

Pin 5

Aux. Fault Relay Common Side of Relay

 

Pin 6 (Right Most)

Aux. Fault Relay NO or NC Side of Relay

 

 

 

 

 

B.2.3 Fault Connector

 

 

 

 

(J4) Fault Relay

Description (Normally Energized State)

 

Pin 1 (Left Most)

Normally Closed Side of Relay

 

 

 

Pin 2 (Middle)

Common Side of Relay

 

 

Pin 3 (Right Most)

Normally Open Side of Relay

 

B.2.4 Power/Communications Connector

 

 

 

 

(J5) Power/Comm.

Description

 

Pin 1 (Left Most) & Pin 5

Power (DC -)

 

Pin 2 & Pin 6

Communication RS 485 (-)

 

Pin 3 & Pin 7

Communication RS 485 (+)

 

Pin 4 & Pin 8 (Right Most)

Power (DC +)

B.2.5 3100-06 Connectors

(J2) Connector

Description

Pin 1 (Left Most)

Power (DC -)

Pin 2

Communication RS 485 (-)

Pin 3

Communication RS 485 (+)

Pin 4

Power (DC +)

Pin 5

4-20mA Negative

Pin 6

4-20mA Positive

Pin 7 to Pin 8 Jumper (Right Most)

Enables 4-20 mA

 

 

Page: 16

Model 3100 Series Flame Detector (11/04)

Page 19
Image 19
Sierra Monitor Corporation 3100-01 Connectors Fire Relay Connector, Verify and Aux. Fault Connector, 5 3100-06 Connectors