Instruction Manual

B.3 Verify/Aux. Relay Configurations

Model #

Verify Relay

Aux. Relay

3100-02

Open Contacts

Closed Contacts

3100-03

Closed Contacts

Open Contacts

3100-04

Open Contacts

Open Contacts

3100-05

Closed Contact

Closed Contacts

B.4 Fault Table

Fault #

Fault Label

Description

1

Lens Test Fault

UV sensors didn’t detect enough UV from the internal UV source.

2

Configuration Fault

SW9 is “ON” or a failed program

3

Calibration Fault

Device is out of calibration

4

Volt. Low

Input Voltage is below 15 VDC

5

Photo. Sensor Fault

IR or Visible sensor failed to detect internal test source.

6

Relay Fault

Relay coil circuit is open.

7

Volt. High

Input Voltage was above 32 VDC

8

Temp. Out of Range

Internal device temperature went below -40° C or above 85° C.

 

 

 

B.5 False Alarm Stimuli Table

FALSE ALARM RESPONSE

This table shows the detectors ability to tolerate both modulated and unmodulated false alarm stimuli.

False Alarms Source

Distance

Unmodulated

Modulated

 

Resistive Electric Heater 1320 Watt

6 Feet

No Response

No Response

 

Fluorescent Lights (2) 40 Watt Bulbs

6 Feet

No Response

No Response

 

Halogen Light 500 Watt

10 Feet

No Response

No Response

 

Incandescent Light 100 Watt

6 Feet

No Response

No Response

 

Arc Welder 50 Watt

25 Feet

No Response

No Response

 

Direct Sunlight

93 million miles

No Response

No Response

 

 

 

 

 

 

B.6 Fire and False Alarm Stimuli Table

Model 3100 detector response to a fire while exposed to a variety of radiant energy sources.

False Alarms

Distance to False

Distance

Response Time to

 

Source

Alarm Source

to Fire

Fire

 

Resistive Electric Heater 1320 Watt

6 Feet

6 Feet

Less than 5 sec.

 

Florescent Lights (2) 40 Watt Bulbs

6 Feet

6 Feet

Less than 5 sec.

 

Halogen Light 500 Watt

10 Feet

6 Feet

Less than 5 sec.

 

Incandescent Light 100 Watt

6 Feet

6 Feet

Less than 5 sec.

 

Arc Welder 50 Watt

25 Feet

6 Feet

Less than 5 sec.

 

Direct Sunlight

93 million miles

6 Feet

Less than 5 sec.

 

 

 

 

 

 

Model 3100 Series Flame Detector (11/04)

Page: 17

Page 20
Image 20