Sierra Monitor Corporation 5000 Cover Plate - Carbon Monoxide Module, SERVICE Page

Models: 5000

1 15
Download 15 pages 61.64 Kb
Page 7
Image 7
Cover Plate - Carbon Monoxide Module

SMC sierra monitor corporation

Sentry Instruction Manual - Version 6

7.7 CARBON MONOXIDE MODULE (5100-04)

7.7.1 DESCRIPTION

The Carbon Monoxide Module includes the sensor and electronic assembly installed in an explosion proof housing.

The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling from the controller connects to a three pin spring loaded terminal strip.

7.7.2 TROUBLE ANALYSIS

Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:

Controller displays the following error messages

SENSOR FAILURE

LOW SENSITIVITY

False readings or alarms are received due to sensor inaccuracy.

Warning: During sensor adjustments the

 

Figure 7-8

concentration reading on the controller will be

Cover Plate - Carbon Monoxide Module

inaccurate and alarm level concentrations may be

 

displayed. If false activation of the alarm relays

 

 

will cause a problem disconnect the relay wiring

 

prior to adjustment or turn the module off using the

• 1 ppm CO = 0.004 VDC.

 

"Change Module" mode.

• 100 ppm CO = 0.40 VDC.

 

 

 

 

 

 

Note

 

• 250 ppm CO = 1.00 VDC.

 

 

Although all the necessary data can be collected with a

 

 

 

 

 

 

 

voltmeter at the sensor module, some helpful information

 

 

 

 

can be displayed on the controller or printed. See

 

7.7.3.2 SENSOR REPLACEMENT

 

 

diagnostic codes 0004 and 0008 in Appendix C.

 

The carbon monoxide sensor should be replaced when it

 

 

 

 

 

 

7.7.3 ADJUSTMENT PROCEDURE

can no longer be calibrated correctly.

Generally this is

Prior to reading voltages and making adjustments perform

every twenty four to thirty months.

 

 

 

a visual inspection to confirm that there are no physical

The "SENSOR FAILURE" message for Carbon

problems such as water in the electronics enclosure,

Monoxide sensors does not indicate a specific failure of

wiring damage or corrosion.

the sensor but indicates that the sensor is not correctly

Use Figure 7-8 to locate test points during the following

connected to the electronics. If this

message appears

procedures.

check that the sensor harness is correctly installed to the

connector on the bottom electronics board.

 

7.7.3.1 SIGNAL ADJUSTMENT

It is unlikely that any electrical adjustment will be required except when a new sensor is installed.

To make the electrical adjustment connect a voltmeter to SIGNAL OUT (pos) and GND (ground) and use SENSITIVITY ADJ potentiometer to adjust the voltage based on the following:

SERVICE

Page: 74

Page 7
Image 7
Sierra Monitor Corporation 5000 Cover Plate - Carbon Monoxide Module, SMC sierra monitor corporation, SERVICE Page