7.7 CARBON MONOXIDE MODULE
7.7.1 DESCRIPTION
The Carbon Monoxide Module includes the sensor and electronic assembly installed in an explosion proof housing.
The sensor screws into one hub of the enclosure and plugs into the bottom electronics card via a six pin connector. Cabling from the controller connects to a three pin spring loaded terminal strip.
7.7.2 TROUBLE ANALYSIS
Electrical adjustment, or replacement of the sensor will be necessary under the following conditions:
•Controller displays the following error messages
SENSOR FAILURE
LOW SENSITIVITY
•False readings or alarms are received due to sensor inaccuracy.
Warning: During sensor adjustments the |
| |
Figure | ||
concentration reading on the controller will be | ||
Cover Plate - Carbon Monoxide Module | ||
inaccurate and alarm level concentrations may be | ||
| ||
displayed. If false activation of the alarm relays |
| |
| ||
will cause a problem disconnect the relay wiring |
|
prior to adjustment or turn the module off using the | • 1 ppm CO = 0.004 VDC. |
| ||
"Change Module" mode. | • 100 ppm CO = 0.40 VDC. |
| ||
|
|
|
| |
| Note |
| • 250 ppm CO = 1.00 VDC. |
|
| Although all the necessary data can be collected with a |
|
| |
|
|
|
| |
| voltmeter at the sensor module, some helpful information |
|
|
|
| can be displayed on the controller or printed. See |
| 7.7.3.2 SENSOR REPLACEMENT |
|
| diagnostic codes 0004 and 0008 in Appendix C. |
| The carbon monoxide sensor should be replaced when it | |
|
|
| ||
|
|
| ||
7.7.3 ADJUSTMENT PROCEDURE | can no longer be calibrated correctly. | Generally this is | ||
Prior to reading voltages and making adjustments perform | every twenty four to thirty months. |
| ||
|
| |||
a visual inspection to confirm that there are no physical | The "SENSOR FAILURE" message for Carbon | |||
problems such as water in the electronics enclosure, | Monoxide sensors does not indicate a specific failure of | |||
wiring damage or corrosion. | the sensor but indicates that the sensor is not correctly | |||
Use Figure | connected to the electronics. If this | message appears |
procedures. | check that the sensor harness is correctly installed to the | |
connector on the bottom electronics board. | ||
|
7.7.3.1 SIGNAL ADJUSTMENT
It is unlikely that any electrical adjustment will be required except when a new sensor is installed.
To make the electrical adjustment connect a voltmeter to SIGNAL OUT (pos) and GND (ground) and use SENSITIVITY ADJ potentiometer to adjust the voltage based on the following: