Sierra Monitor Corporation 5000 instruction manual SMC sierra monitor corporation, SERVICE Page

Models: 5000

1 15
Download 15 pages 61.64 Kb
Page 4
Image 4
1.Scaling factors are not FMRC approved.

SMC sierra monitor corporation

Sentry Instruction Manual - Version 6

7.5.5 COMBUSTIBLE GAS SCALING FACTORS

For combustible gas monitoring, a calibration standard of Methane or Propane my be used in conjunction with scaling factors to cause Sentry concentration display and alarm function in %LEL scale of another gas as follows:

 

GAS

 

METHANE

 

PROPANE

 

 

GAS

 

METHANE

 

PROPANE

 

 

 

 

FACTOR

 

 

FACTOR

 

 

 

 

 

 

FACTOR

 

 

FACTOR

 

 

Acetaldehyde

 

 

60

 

 

109

 

 

 

Diethyl Ether

 

 

46

 

 

84

 

 

Acetic Acid

54

 

98

 

 

 

Dimethoxyethane

42

 

75

 

 

Acetic Anhydride

46

 

83

 

 

 

Dimethyl Ether

63

 

113

 

 

Acetone

52

 

94

 

 

 

Dimethylformamide

46

 

83

 

 

Acetylene

57

 

103

 

 

 

Ethyl Formate

44

 

80

 

 

Alkyl Alcohol

51

 

92

 

 

 

Ethylmercaptan

56

 

102

 

 

Ammonia

126

 

229

 

 

 

n-Heptane

39

 

70

 

 

n-Amyl Alcohol

33

 

59

 

 

 

n-Hexane

37

 

67

 

 

Aniline

39

 

71

 

 

 

Hydrazine

45

 

82

 

 

Benzene

41

 

74

 

 

 

Hydrogencyanide

48

 

86

 

 

Biphenyl

25

 

45

 

 

 

Hydrogen

77

 

139

 

 

1,3-Butadiene

56

 

101

 

 

 

Hydrogen Sulfide

41

 

74

 

 

n-Butane

58

 

106

 

 

 

Methane

100

 

181

 

 

iso-Butane

52

 

94

 

 

 

Methyl Actetate

50

 

90

 

 

Butene-1

45

 

82

 

 

 

Methyl Alcohol

86

 

156

 

 

cis-Butene-2

48

 

88

 

 

 

Methylamine

77

 

140

 

 

trans-Butene-2

51

 

92

 

 

 

Methyl Bromide

90

 

162

 

 

n-Butyl Alcohol

34

 

62

 

 

 

Methyl Chloride

102

 

186

 

 

iso-Butyl Alcohol

53

 

96

 

 

 

Methylcyclohexane

44

 

80

 

 

tert-Butyl-Alcohol

74

 

134

 

 

 

Methylenedichloride

93

 

168

 

 

n-Butyl Benzene

31

 

57

 

 

 

Methylethylether

44

 

80

 

 

iso-Butyl Benzene

32

 

58

 

 

 

Methylethylketone

41

 

75

 

 

n-Butyric Acid

38

 

69

 

 

 

Methyl Formate

67

 

121

 

 

Carbon Disulfide

18

 

32

 

 

 

Methylmercaptan

61

 

110

 

 

Carbon Monoxide

75

 

137

 

 

 

Methylpropionate

51

 

93

 

 

Carbon Oxysulphide

93

 

169

 

 

 

Methyl n-propylketone

40

 

73

 

 

Chlorobenzene

34

 

62

 

 

 

Napthalene

34

 

62

 

 

Cyanogen

89

 

162

 

 

 

Nitromethane

34

 

62

 

 

Cyclohexane

41

 

74

 

 

 

n-Nonane

31

 

57

 

 

Cyclopropane

62

 

113

 

 

 

n-Octane

37

 

68

 

 

n-Decane

33

 

59

 

 

 

n-Pentane

46

 

83

 

 

Diethylamine

49

 

88

 

 

 

i-Pentane

46

 

84

 

 

Dimethylamine

58

 

105

 

 

 

Propane

55

 

100

 

 

2,3-Dimethylpentane

40

 

72

 

 

 

n-Propyl Alcohol

47

 

85

 

 

2,3-Dimethylpropane

40

 

72

 

 

 

n-Propylamine

48

 

88

 

 

Dimethylsulphide

43

 

79

 

 

 

n-Propylchloride

50

 

90

 

 

1,4-Dioxane

45

 

81

 

 

 

Propylene

52

 

93

 

 

Epichlorohydrin

45

 

82

 

 

 

Propyleneoxide

46

 

83

 

 

Ethane

68

 

123

 

 

 

iso-Propylether

44

 

79

 

 

Ethyl Acetate

51

 

93

 

 

 

Propyne

42

 

75

 

 

Ethyl Alcohol

73

 

132

 

 

 

Toluene

40

 

73

 

 

Ethylamine

53

 

95

 

 

 

Triethylamine

40

 

72

 

 

Ethyl Benzene

36

 

65

 

 

 

Trimethylamine

48

 

88

 

 

Ethyl Bromide

91

 

165

 

 

 

Vinylethylether

42

 

76

 

 

Ethyl Chloride

57

 

103

 

 

 

o-Xylene

36

 

65

 

 

Ethylcyclopentane

40

 

72

 

 

 

m-Xylene

39

 

71

 

 

Ethylene

71

 

128

 

 

 

p-Xylene

39

 

71

 

 

Ethylenedichloride

66

 

120

 

 

 

JP-4 (Jet Fuel)

41

 

73

 

 

Ethyleneoxide

52

 

94

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Scaling factors are not FMRC approved.

2.Base data source: EEV sensor specification catalog. (EEV claims some data is the result of specific tests, other data is empirically derived.)

SERVICE Page: 71

Page 4
Image 4
Sierra Monitor Corporation 5000 SMC sierra monitor corporation, Scaling factors are not FMRC approved, SERVICE Page