Slant/Fin V-180, V-33 Pump Zoning system using R845 Relay, One R-845Aneeded for each circulator

Models: V-33 V-180

1 20
Download 20 pages 37.3 Kb
Page 18
Image 18
PUMP OR VALVE ZONING OF WATER BOILERS

PUMP OR VALVE ZONING OF WATER BOILERS

VICTORY

18

 

COMBINATION CONTROLS WITH T TV Z

TERMINALS*

 

 

 

Pump Zoning system using R845 Relay.

One R-845A needed for each circulator.

NOTE: Pumps are powered from C1. Total pump load must not exceed 7.4 amp rating of combination control pump switch.

Zone valve zoning system using Honeywell V8043F zone valves.

Pump zoning system using R8230C Relays.

*For zoning diagrams, combination controls without T TV Z terminals and non-combination control systems, consult Slant/Fin Zoning Technical Bulletin. NOTE: Pumps are powered from C1 . Total pump load must not exceed 7.4 amp rating of combination control pump switch.

Page 18
Image 18
Slant/Fin V-180, V-33 Pump Zoning system using R845 Relay, One R-845Aneeded for each circulator, Terminals