Slant/Fin V-33, V-180 operating instructions All Items Shown Below Are Required

Models: V-33 V-180

1 20
Download 20 pages 37.3 Kb
Page 7
Image 7
Figure 6a.

VICTORY

7

Figure 6a.

Chimney Venting for V-90, V-120, V-150 and V-180 only.

 

Minimum vent connectors diameter is 5 inches. It may have to be upsized to 6 or 7 inches (see Table 1).

 

Single or multiple appliance venting into chimney using single wall or type “B” metal connectors, must be installed

 

in accordance with National Fuel Gas Code ANSI Z223.1-latest edition, part 7 and 11. See “Chimney and Type “B”

 

Venting” paragraph on page 4 of this manual. DO NOT use galvanized risers and connectors in cool boiler rooms.

 

ALL ITEMS SHOWN BELOW ARE REQUIRED.

 

All vent connector joints must be LIQUID tight.

Figure 6b. Venting with “B” vent or metal-lined chimney for V-90, V-120, V-150 and V-180 only

Minimum vent connectors diameter is 5 inches. It may have to be upsized to 6 or 7 inches (see Table 2). Single or multiple appliance venting into Type “B” double wall metal vent with single or Type “B” metal connectors, must be installed in accordance with National Fuel Gas Code ANSI Z223.1-latest edition, part 7 and 11. DO NOT use galvanized risers and connectors in cool boiler rooms.

ALL ITEMS SHOWN BELOW ARE REQUIRED EXCEPT WHERE OTHERWISE INDICATED. All vent connector joints must be liquid tight.

Page 7
Image 7
Slant/Fin V-33, V-180 a, All Items Shown Below Are Required, All vent connector joints must be LIQUID tight