SBN71-120 thru 85-390, SBD30-150/199 TANK TYPE COMMERCIAL

GAS WATER HEATER SERVICE HANDBOOK

9 RULES FOR GOOD VENTING

5.Use a 45° elbow in place of a 90° elbow where possible. Avoid the use of a 90° elbow immediately above the draft hood. Allow the maximum vertical rise before any elbow.

VERTICAL RISE

EQUAL TO

1/4” PER FOOT OF HOROZONTAL RUN

HORIZONTAL RUN

6.Horizontal pipe should be sloped upward at a minimum of ¼” per foot.

State Water Heaters

21

Technical Training Department

Ashland City, Tennessee © 2007

 

 