Sterling GG-105, GG-90 SEPARATED COMBUSTION VENTING continued, Concentric Vent Box Dimensions

Models: GG-105 GG-30 GG-120 GG-45 GG-60 GG-75 GG-90

1 44
Download 44 pages 56.75 Kb
Page 27
Image 27
SEPARATED COMBUSTION

SEPARATED COMBUSTION

VENTING (continued)

4.Use single wall pipe constructed of 26 GA galvanized steel or a material of equivalent durability and corrosion resistance for the vent system. For installations in Canada, use corrosion resistant and gas-tight, listed vent pipe conforming with local building codes, or in the absence of local building codes, with current CAN/CGA-B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment or CAN/ CGA-B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment. For residential installations in the United States, vent pipe approved for Category III appliances must be used between the appliance and the concentric vent box unless 33% of the vent run is vertical, then single wall galvanized vent pipe or double wall Type B vent pipe may be used between the appliance and the concentric vent box. A single length of double wall Type B vent pipe must be used to go through the concentric vent box and outside wall to the vent terminal.

5.Any run of single wall vent pipe passing through an unheated space must be insulated with an insulation

NOTICE: Increasing the clearance distances may be necessary if there is a possibility of distortion or discoloration of adjacent materials.

11.The top of a VERTICALLY VENTED exhaust system must extend at least 3 feet (0.91m) above the roof surface that it passes through. See Figure 22.

12.The point of termination for a HORIZONTALLY VENTED exhaust system must be at least 12 inches (0.3m) from the exterior of the wall that it passes through. In addition, the termination point must be at least 1 foot (0.3m) above grade or above the snow line, more than 6 feet (1.8m) from the combustion air inlet of another appliance, at least 4 feet (1.2m) below, 4 feet (1.2m) horizontally from, or 1 foot (0.3m) above any door, window or gravity air inlet into any building, and more than 3 feet (0.91m) from and not directly above, any gas meter or service regulator. See Figures 23 and 24 and Table 4.

 

suitable to 550° F.

 

Table 6 - Concentric Vent Box Dimensions

 

6.

The vent system must be installed to prevent

 

Unit

 

Dimensions - Inches (Nominal)

 

 

collection of condensate. Pitch horizontal pipes

 

 

 

 

 

 

 

 

 

 

downward 1/4 inch per foot (21mm per meter) toward

Size

A

B

C

D

E

G

 

30

 

 

 

 

 

 

 

the vent cap to facilitate drainage. Vertical vent pipes

 

 

 

 

 

 

 

should be piped as depicted in Figure 22.

 

45

41/2

4

6

8

5

12

7.

The equivalent length of the vent system must not be

60

 

 

 

 

 

 

 

less than 5 feet (1.5m) and must not exceed 30 feet

75

 

 

 

 

 

 

 

(9m). The equivalent length equals the total length

90

 

 

 

 

 

 

 

of straight pipe plus 5 feet (1.5m) for each 90° elbow

 

 

 

 

 

 

 

105

51/2

5

8

12

5

15

 

and 2.5 feet (0.76m) for each 45° elbow.

 

120

 

 

 

 

 

 

8.

Each slip joint must be secured with at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

least three corrosion resistant screws.

 

 

 

 

 

 

 

 

 

Two full turns of 3M #425 Aluminum Foil

Figure 20 - Concentric Vent Box

 

 

 

 

 

tape or its equivalent must then be used

 

 

 

 

 

to seal each joint. High temperature

 

 

 

 

 

 

 

 

 

silicone sealant may be used instead of

 

 

 

 

 

 

 

 

 

the tape. Silicone sealant must be used

 

 

 

 

 

 

 

 

 

to seal the joint between the Type B vent

 

 

 

 

 

 

 

 

 

pipe and the single wall pipe.

 

 

 

 

 

 

 

 

9.

For horizontal vent systems longer

 

 

 

 

 

 

 

 

 

than 5 feet (1.5m), the system must

 

 

 

 

 

 

 

 

 

be supported from overhead building

 

 

 

 

 

 

 

 

 

structures at 4 foot (1.2m) intervals in

 

 

 

 

 

 

 

 

 

the U.S. and at 3 foot (0.91m) intervals in

 

 

 

 

 

 

 

 

 

Canada.

 

 

 

 

 

 

 

 

10.

The exhaust vent system must remain

 

 

 

 

 

 

 

 

 

at a minimum distance of 1 inch (25mm)

 

 

 

 

 

 

 

 

 

from all combustible materials. Any part

 

 

 

 

 

 

 

 

 

of the vent system that passes through

 

 

 

 

 

 

 

 

 

a combustible material must be properly

 

 

 

 

 

 

 

 

 

insulated.

 

 

 

 

 

 

 

 

27

Page 27
Image 27
Sterling GG-105, GG-90, GG-75, GG-60, GG-45, GG-120 SEPARATED COMBUSTION VENTING continued, Concentric Vent Box Dimensions