Sterling RF-75, RF-60, RF-90, RF-45, RF-30 Vertically Vented Unit Heaters Category, Venting

Models: RF-30 RF-45 RF-75 RF-90 RF-60

1 32
Download 32 pages 53.62 Kb
Page 12
Image 12
VENTING

VENTING

ANSI now organizes vented appliances into four categories.

Venting Categories

 

Non

 

 

Condensing

Condensing

Negative

 

 

Vent

I

II

Pressure

 

 

Positive

 

 

Vent

III

IV

Pressure

 

 

Category I

Category III

Includes non-condensing

Appliances are non-condensing

appliances with negative vent

and operate with a positive vent

pressure, like the traditional

pressure.

atmospheric unit heater.

Category IV

Category II

Covers condensing appliances

Groups condensing appliances

with positive vent pressure.

with negative vent pressure.

NOTICE: Category II and IV do

 

 

not apply to equipment specified

 

within this manual.

VERTICALLY VENTED UNIT HEATERS

(CATEGORY I)

Observe the following precautions when venting the unit: The unit heater shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.

Venting into an unlined masonry chimney is prohibited.

1.Use flue pipe of the same size as the flue connections on the gas unit heater, 4 inch (102mm). All heaters must be vented with UL Listed Type B vent, or single wall pipe.

2.Provide as long a vertical run of flue pipe at the gas unit heater as possible. A minimum of 5 feet (1.5m) of vertical flue is required. The top of the vent pipe should extend at least 2 feet (0.61m) above the highest point on the roof. Install a weather cap over the vent opening.

3.Slope horizontal runs upward from the gas unit heater at least 1/4-inch per foot (21mm/m) minimum. Horizontal runs should not exceed 33% of the vertical height of the vent pipe, or chimney, above the flue pipe connection, up to a maximum length of 10 feet (3m). Horizontal portions of the venting system shall be supported at maximum intervals of 4 feet (1.22m). (See Figure 12)

4.Use as few elbows as possible.

5.Tape flue pipe joints with high temp, RTV or foil face tape.

6.Avoid running vent pipe through unheated spaces.

7.When this cannot be avoided, insulate the pipe to prevent condensation of moisture on the walls of the pipe. Insulate vent pipe runs longer than 10 feet (3m). Insulation should be a minimum of 1/2 inch (12.7mm) thick foil faced fiberglass, 1-1/2# density insulation.

8.Do not damper the flue piping. Failure to open such a damper prior to operating the gas unit heater will result in the spillage of flue gas into the occupied space.

9.Avoid installing units in areas under negative pressure due to large exhaust fans or air conditioning. When required, a flue vent fan should be installed in accordance with the instructions included with the fan.

10.Vent connectors serving Category I and Category II heaters shall not be connected into any portion of mechanical draft systems operating under positive pressure.

11.Also refer to Figures 17 and 19 for additional requirements.

Figure 12

12

Page 12
Image 12
Sterling RF-75, RF-60, RF-90, RF-45, RF-30 specifications Vertically Vented Unit Heaters Category, Venting