2.ADDITIONAL VENTILATION

PRE-INSTALLATION CHECKS

Model

 

 

 

Sheraton

 

 

 

 

Sheraton - 7016 / 7017 / 7027

 

 

 

 

Without liner system

 

mm

150

 

 

 

 

 

 

 

 

 

 

 

round (diameter)

 

inch

6

 

 

 

 

 

 

 

 

Flue/Chimney

Without liner system (square)

 

mm

135

 

 

 

Size

minimum dimension

 

inch

51/2

 

 

 

 

With liner or factory made

 

mm

150

 

system (diameter)

 

 

 

 

 

 

6

 

installed in accordance with manufacturers instructions

 

inch

 

 

 

 

 

Flue/Chimney

minimum height*

m4.5

feet 15

*When measured from the top of the stove to the top of the flue, with no horizontal sections and a maximum of 4 bends with angles of less than 45°

2.ADDITIONAL VENTILATION

2.1Additional ventilation will be required to comply with the requirements of the Building Regulations. This should be provided using a permanently open air vent, of the size listed, which is positioned so that it is not liable to be blocked both inside and outside the building.

2.2Extractor fans or cooker hoods should not be placed in the same room or space as the appliance.

2.3If any of these checks reveal problems do not proceed with the fitting of the appliance until they have been rectified.

Model

 

Sheraton

Sheraton - 7016/7017/7027

 

 

 

 

 

 

 

mm2

1650

Additional Ventilation

cm2

16.5

 

in2

2.55

14

Page 14
Image 14
Stovax 7017, 7016, 7027, sheraton free standing stove manual Additional Ventilation, Pre-Installationchecks, Sheraton