Model |
|
|
| Sheraton |
|
|
|
| |
Sheraton - 7016 / 7017 / 7027 |
|
|
| |
| Without liner system |
| mm | 150 |
|
| |||
|
|
|
| |
|
|
|
| |
| round (diameter) |
| inch | 6 |
|
|
| ||
|
|
|
|
|
Flue/Chimney | Without liner system (square) |
| mm | 135 |
|
|
| ||
Size | minimum dimension |
| inch | 51/2 |
|
|
| ||
| With liner or factory made |
| mm | 150 |
| system (diameter) |
|
|
|
|
|
| 6 | |
| installed in accordance with manufacturers instructions |
| inch | |
|
|
|
|
|
Flue/Chimney
minimum height*
m4.5
feet 15
*When measured from the top of the stove to the top of the flue, with no horizontal sections and a maximum of 4 bends with angles of less than 45°
2.ADDITIONAL VENTILATION
2.1Additional ventilation will be required to comply with the requirements of the Building Regulations. This should be provided using a permanently open air vent, of the size listed, which is positioned so that it is not liable to be blocked both inside and outside the building.
2.2Extractor fans or cooker hoods should not be placed in the same room or space as the appliance.
2.3If any of these checks reveal problems do not proceed with the fitting of the appliance until they have been rectified.
Model |
| Sheraton |
Sheraton - 7016/7017/7027 |
| |
|
| |
|
|
|
| mm2 | 1650 |
Additional Ventilation | cm2 | 16.5 |
| in2 | 2.55 |
14