Sunrise Global 13-05020 Airpurgingandleakagetest, Outdoor condensation drainage, Installation

Models: 13-05020 13-05024

1 24
Download 24 pages 28.37 Kb
Page 21
Image 21
AIRPURGINGANDLEAKAGETEST

Outdoor condensation drainageInstallation:Manual backgroundManual backgroundManual backgroundManual backgroundAIRManual backgroundManual backgroundManual backgroundManual backgroundPURGINGManual backgroundManual backgroundManual backgroundANDManual backgroundManual backgroundManual backgroundManual backgroundLEAKAGEManual backgroundManual backgroundManual backgroundManual backgroundTESTManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

1.Take out the nut cover of the inlet for refrigerant.

2.Connect the tube of the vacuum watch with the vacuum pump, having the low- pressure end linking to the inlet for refri- gerant.

3.Starting the vacuum pump, when the indicator turns to -1 bar, closing the low pressure handle and stopping vacuu- mize. Keep for 15 minutes, ensuring the pressure of the vacuum watch remains.

4.Take out the valve cover of the gas valve and also the one for the liquid valve.

5.Loosing the cord of liquid valve until the pressure rise to 0 bar.

6.Dismantle the tube from the cover of the inlet for refrigerant then, tighten the cover.

7.Loose the valve cord of the gas valve as well as the liquid valve entirely.

8.Tighten the valve cover of the gas valve and liquid valve so as to check whether leakage occurred.

Pressure gauge

Nut

Vacuum pump

Liquid

pipe Gas pipe

Outdoor condensation drainage

When the unit is cooling or defrosting, the waste water formed in the outdoor unit can be drained out reliably through the drain hose.

Installation:

Install the outdoor drain elbow in the 25 mm (1”) hole on the base plate as

shown in Fig.8, and joint the drain hose to the elbow, so that the waste water formed in the outdoor unit can be drained out to a proper place.

Base plate

Outdoor drain elbow

20

Page 21
Image 21