Disable the Shelf Manager on the SCM
6. | To determine the version of SCM’s | |||
| rsys_debug |
|
| |
7. | After determining the version, enter the appropriate command. | |||
|
|
|
|
|
| For version | Enter this command | Result |
|
| 0.96 or below | rsys_debug | Takes you directly to IPMI serial interface. |
|
| 0.97 or above | rsys_debug | Enables LAN access. |
|
8. | Once the software tool has completed its initialization, the host address is displayed. Make a note | |||
| of this address for an upcoming step. Typically the address is located at either 0x82 or 0x84. | |||
9. | At the cmd prompt, enter m. |
|
| |
10. | At the menu prompt, enter 40. |
|
| |
11. | The following prompt displays: |
|
| |
| Set SCM ShMgr Mode - |
|
| |
| Enter address (in hex): |
|
|
Enter the host address you previously noted for step 8 in hex format. For example, if the address listed was 0x82, enter 82.
12. The following prompt displays:
Enter ShMC Mode (Enable 0, Disable 1):
Enter 1 to disable the
13.To verify the
14.The following text displays:
Get SCM ShMgr Mode -
Enter address (in hex):
Enter the same host address you entered for step 11. If the
SCM ShMgr Mode: Disabled
15.Enter q to exit the rsys_debug mode.
16.If a second SCM is installed, connect to it and run through the same set of procedures described in steps 1 through 15.
17.Cycle the power on the shelf to restart the
18.Verify switch operation. See page 7 for more information.