INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range
Before installing detectors, please thoroughly read the NEMA Guide for Proper Use of Smoke Detectors in Duct Applications, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from NEMA (National Electrical Manufacturers Association, 2101 L Street NW, Washington, DC 20037). NFPA Standards 72 and 90A should also be ref- erenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly fol- lowing NFPA 72 requirements. The detector should be cleaned at least once a year.
General Description |
|
|
|
|
|
| The DH200RPL incorporates a cover tamper feature. When the cover is |
|
|
|
|
|
|
| |
An HVAC system supplies | conditioned air to | virtually every | area of | removed for more than 20 minutes, the unit loses communication at the | |||
| |||||||
a building. Smoke introduced into | this air | duct system | is | distrib- | panel, a trouble is indicated at the panel and the alarm relay switches | ||
| |||||||
uted to the entire building. Smoke | detectors | designed for | use | in air | states thereby shutting down fans, dampers and blowers. In the case | ||
| |||||||
duct systems are used to | sense the | presence | of smoke in | the | duct. | when the sensor is removed or when there is no power to the unit, only a | |
|
trouble is indicated at the panel (alarm relay does not work any longer).
Contents of the Duct Smoke Detector Housing Kit
The DH200RPL Duct Smoke Detector consists of the following items
(See Figure 1.):1. Complete duct smoke detector assembly with
Figure 1. Exploded View Of Duct Smoke Detector Components: |
| sensor | |
FOAM |
| 2. | Two #10 x 11⁄4″ sheet metal mounting screws |
GASKETS |
| 3. | Two sampling tube filters |
|
| ||
| CONDUIT HOLES | 4. | One test magnet |
|
|
| |
SAMPLING TUBE | DETECTOR | 5. | Drilling template |
HOUSING |
|
| |
FILTERS |
| 6. | Two foam gaskets |
|
| ||
|
| 7. | Four |
SAMPLING TUBE | TERMINAL STRIP |
| sampling tube and optional exhaust tube |
|
| ||
| POWER BOARD |
| extension |
|
|
| |
|
| 8. | One sampling tube end cap |
| COVER MOUNTING | 9. | One plastic sampling tube |
| SCREWS | 10. | One #8 |
|
|
DETECTOR BOARD | tube |
|
DETECTOR
COVER
NOTE: For ducts over 11⁄2 feet (0.46m), longer sampling tubes must be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.
1 |