System Sensor DH200RPL Sampling tube filter installation, Wiring Instructions, Install The Cover

Models: DH200RPL

1 8
Download 8 pages 44.46 Kb
Page 4
Image 4
[5] Install The Filters

NOTE: Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these cases a 3 inch (75mm) floor flange (available at most plumb- ing supply stores) may be used to fasten the sampling tube to the other side of the duct. When using the flange/connector mounting technique, drill a 1-inch to 114-inch (25 to 32mm) hole where the flange will be used.

[5] Install The Filters

To install the sampling tube filters, simply push the filters into the sam- pling and exhaust tube holes, as shown in Figure 6. If a metal sampling tube is used, install the filters into the tube end.

Figure 6. Sampling tube filter installation: CAUTION

Filters require periodic cleaning or replacement, depending on the amount of dust and dirt accumulated. Visually inspect the filters at least quarterly; inspect them more often if the dust accumulation warrants it. See Section [9.1.2] for more information. Replacement filters can be ordered (filter P/N F36-09-11).

Figure 6. Sampling tube filter installation:

[6] Field Wiring Installation Guidelines

Two LEDs on each duct smoke detector may light, if programmed by the system control panel, to provide a local, visible indication. Remote LED annunciator capability is available as an option. Each duct smoke detector can only be wired to one remote accessory.

Different panel manufacturers offer different feature sets across their dif- ferent panel models. As a result, certain features of the DH200RPL may be available on some control panels, but not on others. The possible features available in the DH200RPL, if supported by the control panel are:

1.Panel controls the LED operation on sensor. Operational modes are RED blink, RED continuous, and off.

2.The remote output of the RA400Z does not follow the condition of the duct smoke detector LED while in standby. When in alarm, the LED output of the detector and remote will be identical.

Please refer to the operation manual for the UL

listed control panel for specific operation of the DH200RPL.

Wiring Instructions

Disconnect power from the communication line before installing the DH200RPL duct smoke detector.

Wire the DH200RPL duct smoke detector per the Control Panel Installation Manual and Figures 9, 10 or 11.

Set the desired address on the sensor board address code wheel switches (see Figure 7).

All wiring must be installed in compliance with the National Electrical

 

Figure 7. Rotary Address Switches

Code and the local codes having jurisdiction. Proper wire gauges should

 

 

be used. The conductors used to connect smoke detectors to control

[7] Perform Detector Check

panels and accessory devices should be color-coded to prevent wiring

1.

Perform STANDBY AND TROUBLE TEST per Section [9.2.1].

mistakes. Improper connections can prevent a system from responding

2.

Perform MAGNET TEST per Section [9.2.2.1]. The

properly in the event of a fire.

 

RTS451 test of Section [9.2.2.2] may substitute for this requirement.

For signal wiring, (the wiring between detectors or from detectors to auxil-

3.

Perform AIR FLOW TEST per Section [9.1].

iary devices), it is usually recommended that single conductor wire be no

4.

Perform SMOKE RESPONSE TEST per Section [9.1.1].

smaller than 18 gauge. The duct smoke detector terminals accommodate

[8] Install The Cover

wire sizes up to 12 gauge. The last foot (0.3m) of conduit should be flex-

Install the cover using the six screws that are captured in the housing

ible conduit (available in electrical supply houses), which facilitates easier

cover. Be certain filters are installed as specified in Section [5]. Make sure

installation and puts less strain on the conduit holes in the housing. Solid

that the cover fits into the base groove and that all gaskets are in their

conduit connections may be used if desired.

proper positions. Tighten the six screws.

Smoke detectors and alarm system control panels have specifications for

[9] Duct Smoke Detector Maintenance and Test Procedures

Signaling-Line Circuit (SLC) wiring. Consult the control panel manufactur-

Test and maintain duct smoke detectors as recommended in NFPA 72. The

er’s specifications for wiring requirements for the particular model control

tests contained in this manual were devised to assist maintenance person-

panel being used before wiring the detector loop.

nel in verification of proper detector operation.

The DH200RPL detector is designed for ease of wiring. The housing

Before conducting these tests, notify the proper authorities that the smoke

provides a terminal strip with clamping plates. Wiring connections are

detection system will be temporarily out of service. Disable the device or

made by stripping about 38-inch (9mm) of insulation from the end of the

system under test to prevent unwanted alarms.

wire, sliding the bare end under the plate, and tightening the clamping

 

 

plate screw.

 

 

 

 

 

D200-39-00

4

I56-1977-004R

Page 4
Image 4
System Sensor DH200RPL Sampling tube filter installation, Wiring Instructions, Rotary Address Switches, Install The Cover