System Sensor DH200RPL manual 9.2.2.2 RTS451/RTS451KEY Remote Station Test, Sensitivity Tests

Models: DH200RPL

1 8
Download 8 pages 44.46 Kb
Page 7
Image 7

[9.2.2.2] RTS451/RTS451KEY Remote Station Test

The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct smoke detector. These accessories provide the stimulus to initiate an alarm condition at the detector. The detector is self-restoring when the accessory test stimulus is removed. Verify that the system control panel has reset; panel may need to be reset.

[9.2.3] Sensitivity Tests

Notify the proper authorities that the smoke detector system is undergo- ing maintenance, and that the system will temporarily be out of service. Disable the device or system undergoing maintenance to prevent unwant- ed alarms and possible dispatch of the fire department.

[9.3] Maintenance of Duct Smoke Detectors [9.3.1] Air Filters

1.Turn off power to the system.

2.Remove and inspect sampling tube filters.

3.If filters are heavily coated with dirt, replace them with new filters (p/n F36-09-11). If they are not heavily coated, use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.

[9.3.2] Photo Detector Boards

1.Remove the screen by gently grasping on each side and pulling straight off

2.Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and blow out any remaining debris. Replacement screens (p/n S08-39-01) are available.

3.Vacuum photo chamber, then use clean compressed air to blow area clean.

4.Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.

[10] Board Replacement

[10.1] Sensor Board Replacement

1.Remove the two sensor board mounting screws.

2.Pull gently on the board to remove it.

3.To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.

4.Secure board with the two mounting screws.

[10.2] Power Board Replacement

1.Disconnect wiring from the terminal block.

2.Remove the two power board mounting screws.

3.Pull gently on the board to remove it.

4.To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.

5.Secure board with the two mounting screws.

6.Re-connect wiring to terminal block.

[11]Model DH200RPL Air Duct Smoke Detector Specifications

Operating Temperature Range 32° to 131°F (0° to 55°C)

Storage Temperature Range

-22º to 158ºF (-30º to 70ºC)

Humidity Range

10% to 93% (non-condensing)

Air Velocity

100 to 4000 ft/min (0.5 to 20.32 m/sec.)

Dimensions

1438L x 512W x 234D (37 cm L x

 

14 cm W x 7 cm D)

D200-39-00

7

I56-1977-004R

Page 7
Image 7