OPERATION MANUAL | PROGRAM PARAMETERS | |
|
|
|
Parameter | Description | FactoryDefault |
|
|
|
EX_TPS
TPSCAL
External Temperature Span. The External Temperature Span is the upper range setting for the external
English Unit Version: 0.000 to 990.0000 degrees F.
Metric Unit Ver sion: 0.000 to 990.0000 de grees C.
Temperature Span Calibration. The Temperature Span Calibration Value is the 20 milliamp (span) count value from the external
200.0000
21000
If an external temperature op tion is
APRSRC
APRCON
EX_APZ
Absolute Pressure Source. Available assignments are 0 = CONstant 0 = CONstant
and 1 = EXTernal. þNote: MST2000 DP sen sor max i mum op er at ing static pres sure is 25 PSID.
Absolute Pressure Constant. The absolute pressure constant can | 14.6960 for English. |
be used for mass flow calculations when no external absolute pressure | 1.01325 for Metric. |
input is available and is entered as the average absolute pressure |
|
inside the duct. The avail able range is: |
|
English Unit Version: 0.000 to 100.0000 PSIA. |
|
Metric Unit Ver sion: 0.000 to 100.0000 Bar. |
|
External Absolute Pressure Zero. The External Absolute Pressure | 0.000 |
Zero is the lower range (4 milliamp zero) setting for the external |
|
milliamp ‘absolute pressure’ input channel. The avail able range is: |
|
English Unit Version: 0.000 to 100.0000 PSIA. | þNote: MST2000 DP sensormaximum |
Metric Unit Ver sion: 0.000 to 100.0000 Bar. | op er at ing static pres sure is 25 PSID. |
APZCAL
EX_APS
Absolute Pressure Zero Calibration The Absolute Pressure Zero Calibration value is the 4 milliamp (zero) count value from the external
External Absolute Pressure Span. The External Absolute Pressure Span is the upper range setting for the external
4175
If an external absolute pressure option is
25.0000 for English.
1.7237 for Metric
English Unit Version: 0.000 to 100.0000 PSIA. | þNote: MST2000 DP sensormaximum |
Metric Unit Ver sion: 0.000 to 100.0000 Bar. | op er at ing static pres sure is 25 PSID. |
Brandt Instruments, Inc. | MST2000 Multivariable SMARTFLOW ® Transmitter | Page 15 |