PROGRAM PARAMETERS | OPERATION MANUAL | |
|
|
|
Parameter | Description | FactoryDefault |
|
|
|
APSCAL
Absolute Pressure Span Calibration. The Absolute Pressure Span Calibration value is the 20 milliamp (span) count value from the external
21000
If an external absolute pressure option is
INPUTO
INPUTG
Input Offset. The Input Offset parameter allows the user to adjust (calibrate) the actual pressure (zero) value to the MST2000 displayed value. The input offset parameter is displayed and stored in memory as counts. After the EDIT key is pressed, the edit menu displays the real time pressure input. The user then uses the INC and DEC keys to adjust the desired offset. The pressure input must be connected to a pressure source and be at minimum range value (zero reference) during this adjustment. Use the MODE key to adjust the cursor position ( i.e.. x D1, x D10, x D100, etc.) to change the offset count by different increments. The available range is
Input Gain. The Input Gain parameter allows the user to adjust the gain of the actual pressure (full scale) value to the MST2000 displayed value. The input gain parameter is displayed and stored in memory as a gain multiplier. After the EDIT key is pressed, the edit menu displays the real time pressure input. The user then uses the INC and DEC keys to adjust the desired gain. The pressure input must be connected to a pressure source and at maximum range value during this adjustment. Use the MODE key to adjust the cursor position (i.e.., x D1, x D01, x D001 etc.) to change the gain multiplier by different increments. The available range is 0.8000 to 1.2000 (approximately +/- 20 % adjustment of full scale). The factory default is as set by the factory during initial system calibration.
This is a factory default setting determined during calibration. It should be recorded by the user in the event it will be necessary to restore the Input Offset to the original value. This setting is also recorded on a label located under the cover of the MST2000.
This is a factory default setting determined during calibration. It should be recorded by the user in the event it will be necessary to restore the Input Gain to the original value. This setting is also recorded on a label located under the cover of the MST2000.
OUTPTO
Output Offset. The Output Offset parameter allows the user to adjust the actual 4 milliamp (zero) output value as referenced to the MST2000 displayed zero value. The output offset parameter is displayed and stored in memory as counts. After the EDIT key is pressed, the edit menu displays the actual count offset and the microprocessor sets the output to the 4.000 milliamp value. The user then presses the INC and DEC keys to adjust the desired milliamp offset. Use the MODE key to adjust the cursor position (i.e. x D1, x D10, x D100, etc.) to change the offset count by different increments. The available range is
This is a factory default setting determined during calibration. It should be recorded by the user in the event it will be necessary to restore the Output Offset to the original value. This setting is also recorded on a label located under the cover of the MST2000.
Page 16 | MST2000 Multivariable SMARTFLOW ® Transmitter | Brandt Instruments, Inc. |