Kohler 10ERG, 15ERG manual Appendix A Generator Selection and Wattage Requirements, Appliance Loads

Models: 10ERG 13ERG 15ERG

1 52
Download 52 pages 37.64 Kb
Page 47
Image 47
Appendix A Generator Selection and Wattage Requirements

Appendix A Generator Selection and Wattage Requirements

General Wattage Requirements

Appliance Loads

Consider the total wattage requirements (lights, motors, appliances) when selecting a generator set, or when sizing wattage usage in which available space and construction limit the size of the generator set.

Motor Loads

When figuring generator set capacity requirements for loads that include electric motors, consider the high current demanded by the motors during startup. The inrush or starting current is typically 2 to 3 times higher than that required when the motor reaches normal operating speed. Allow a reserve for inrush demands plus other loads that could be on the line as the electric motor starts. Use Figure 1 as a guide when selecting generator set capacity requirements involving motor loads.

 

Starting

 

Motor

(Inrush)

Running

HP

Watts

Watts

 

 

 

1/4

750

330

 

 

 

1/3

1000

400

 

 

 

1/2

1500

600

 

 

 

3/4

2000

750

 

 

 

1

3300

1100

 

 

 

2

4000

2000

 

 

 

3

5000

3000

 

 

 

Figure 1 Motor Requirements

Generator sets often furnish AC for appliances such as TVs, stereos, and electric water heaters. Except for the resistance-type loads such as the water heater, the requirements for appliances are usually low. Do not overlook such loads when figuring the total requirements. Allow a reserve capacity for anticipated appliance loads to avoid overloading a generator set.

Lighting Load

To calculate the lighting load, add the wattage of each generator set-operated lamp. Note that not all of the lights or lamps are on the generator set AC circuit—some are DC powered by a 12-volt battery. Ensure that the calculated total wattage includes only lights actually on the generator set AC circuit.

Air Conditioners

The starting characteristics of air conditioners vary greatly—for example, one 12,000 Btu unit has lower starting requirements than a 10,000 Btu unit of another variety. When using only one unit, there is usually no starting problem provided that the lighting and appliance load is not too high when starting the generator set.

Simultaneous starting of two air conditioning units, however, can present problems if the generator set capacity is marginal. Because of the variation in starting characteristics among air conditioners, this publication makes no statements regarding multiple-motor starting capabilities of the generator set covered. Consider delayed starting or the use of easy-starting devices on air conditioner units whenever simultaneously starting more than one motor.

See Figure 2 for typical air conditioner requirements. The requirements vary among different manufacturers.

Air Conditioner Size (Btu)

 

7,000

9,000

12,000

16,000

24,000

 

 

 

 

 

 

 

 

 

 

Voltage

115

230

115

230

115

230

115

230

230

 

 

 

 

 

 

 

 

 

 

Full load amps

9.3

4.8

9.9

5.0

11.8

6.3

16.3

8.0

11.6

 

 

 

 

 

 

 

 

 

 

Rated load amps

7.7

4.0

7.0

3.5

8.9

4.8

13.0

6.2

10.2

 

 

 

 

 

 

 

 

 

 

Locked rotor amps

34.0

20.0

40.0

20.0

50.0

31.0

75.0

36.0

56.0

 

 

 

 

 

 

 

 

 

 

Starting (inrush) watts

3910

4600

4600

4600

5750

7130

8630

8280

12,900

 

 

 

 

 

 

 

 

 

 

Running watts

886

920

805

805

1020

1100

1500

1430

2350

 

 

 

 

 

 

 

 

 

 

Figure 2 Typical Air Conditioner Requirements (60 Hz)

TP-6335 9/04

Appendix A-1