8.1 Four-Lead Reconnection

8.1 Four-Lead Reconnection

The following drawings illustrate the reconnection of four-lead generator sets. In all cases, conform to the National Electrical Code (NEC).

NOTICE

Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.

100-120-Volt Configurations

If the installation requires a factory two-pole circuit

100-120/200-240-Volt Configurations

The 100--120/200--240-volt configuration does not use a jumper lead. If the unit was originally wired for straight 100--120 volt, 3 wire, remove the jumper lead (see Figure 8-1 for location). Select a two-pole circuit breaker. Application of two single-pole circuit breakers does not conform to NEC requirements for supplying a 200--240 volt load—even if the breakers are mechanically attached. Leads L1 and L2 are for different phases—never connect them.

L0 (Neutral)

L0

breaker, do not connect the load-side terminals of the circuit breaker. See Figure 8-1. If the installation requires a 100--120-volt, 2-wire system, use a single-pole circuit breaker. See Figure 8-2. When connecting stator phase leads together, size the output lead (L1) to handle the amperage. Use a jumper lead on the line side of the circuit breaker to balance the load of the generator set.

L0 (Neutral)

L0

 

Ground

GRD.

 

 

L1

 

L2

Ground

Load

Side

Line

Side

4 3 2 1

Stator Leads

60 Hz

GRD.

L1

Single-Pole

Circuit

Breaker

Load

 

Side

 

 

Two-Pole

Line

Circuit

 

Side

Breaker

 

L0--L1 100--120 Volt

L0--L2 100--120 Volt

Figure 8-2 100--120-Volt, 2-Wire Configuration

L0 (Neutral)

L0

Jumper

Lead

4 3 2 1

Figure 8-1 100--120-Volt, 3-Wire Configuration

Manual background Ground

Load

Side

Line

Side

GRD.

L2

L1

Factory

Two-Pole

Circuit

Breaker

100-120/200-240 Volt,

43 2 1 3 Wire

Stator Leads

60 Hz

L0--L1 100--120 Volt

L0--L2 100--120 Volt

L1--L2 200--240 Volt

Figure 8-3 100--120/200--240-Volt, 3-Wire Configuration

26 Reconnection/Adjustments

TP-6335 9/04