Parameter

Setting

Definition

 

 

 

 

Unit’s system voltage

Uu01

Single phase, 60 Hz, 120/240 VAC

and frequency

 

 

 

 

 

 

Unit configuration

Uc02

Mobile generator set

 

 

 

Engine type

Ec03

10/13/15ERG

 

 

 

Engine data input types

Ed00

All digital inputs

(No magnetic pick-up)

 

 

 

Ed01

Digital:

Low coolant level and low oil pressure

 

 

 

Analog:

Low coolant temperature

 

 

 

 

 

Ed02

Digital:

Low coolant level and low coolant temperature

 

 

Analog:

Low oil pressure

 

 

 

 

 

Ed03

Digital:

Low coolant level

 

 

Analog:

Low coolant temperature and low oil pressure

 

 

 

 

 

Ed08

Digital:

Low coolant temperature and low oil pressure

 

 

Analog:

Low coolant level

 

 

 

 

 

Ed09

Digital:

Low oil pressure

 

 

Analog:

Low coolant level and low coolant temperature

 

 

 

 

 

Ed10

Digital:

Low coolant temperature

 

 

Analog: Low coolant level and low oil pressure

 

 

 

 

Ed11

All analog inputs

 

 

 

Battery voltage

Bt12

Battery voltage 12 VDC

 

 

 

Communications

Cn00

No CAN communications

 

 

 

 

Cn01

SAE J1939 (Used for ADC remote digital gauge)

 

 

 

 

Cn02

Future CANbus

Figure 8-8 Controller Parameters

TP-6335 9/04

Reconnection/Adjustments 33

Page 43
Image 43
Kohler 13ERG, 15ERG, 10ERG manual Controller Parameters