Controller Configuration Mode (Use with Figure 8-8, Controller Parameters):

Hold the Select button:

Move the generator set master switch to the RUN position. (The generator set engine will not start.)

Wait about 5 seconds until the display shows the program version number. (The number may be different than the one shown here.)

Press the down arrow key and then the up arrow key 3 times to enter the configuration mode. (This is the controller “password.”)

Now release the Select button.

Press:

or

To set the voltage/frequency setting for 60 Hz

models.

 

 

To step to the next parameter, unit configuration

 

Uc.

or

To set the unit configuration setting to Uc02, if

necessary.

 

 

To step to the next parameter, engine type Ec.

or

To set the engine type, if necessary.

 

To step to the next parameter, advanced

 

configuration mode or save mode selection.

Now either save your settings or enter the Advanced Configuration Mode to set the engine data inputs, battery voltage, and communications.

Press:

 

 

To enter advanced configuration mode.

 

Go to Figure 8-10.

OR:

 

or

To proceed to the save mode without

 

entering the advanced configuration mode.

 

Go to Figure 8-7.

Display:

. 0

1 0 4

U u 0 x

U u 0 1

U c 0 2

E c 0 3

A d n c

E d 0 x

S A V E

Note: Shaded boxes show which number in the controller display changes when the up or down arrow key is pressed. “x” denotes any number from 0 to 9.

Figure 8-9 Configuration Mode (system voltage, unit configuration, and engine type parameters)