8.2Advanced Digital Control (ADC 2100)
The model 10/13/15ERG generator sets use the ADC 2100. The ADC 2100 uses
This section contains instructions for using the ADC’s
DCheck and adjust the controller configuration and generator output after generator set reconnection to a different voltage.
DCheck the controller configuration when troubleshooting generator set problems.
DCheck and adjust the generator set output after installation if the voltage requires adjustment for a particular application.
8.2.1Configuration Mode Time Out
The controller will automatically exit the configuration mode without saving any changes after about 1 minute if no buttons are pressed. Start the configuration procedure over again from the beginning if the controller exits the configuration mode before the settings have been saved.
8.2.2Controller Software Version Number
The application software for controller operation is
The controller’s application software version number is displayed on the LED screen during the key sequence to enter the configuration mode, after the Select button has been pressed and held for about five seconds. For example, 01.00 will be displayed for software version 1.00.
28 Reconnection/Adjustments |