Tamron MST2000 operation manual 16.2DP CALIBRATION

Models: MST2000

1 33
Download 33 pages 61.13 Kb
Page 33
Image 33

Cal i bra tion of the MST2000

OPERATION MANUAL

16.2DP CALIBRATION

þNOTE: For MST2000 Trans mit ters with CONTINUOUS PURGE OPTION. Do not use a hand pump, or com- pres sion cyl in der type of pres sure source for the DP test sig nals. You must use a vented source to per- mit con tin u ous flow of purge air. Con tact the fac tory for ad di tional in for ma tion on calibrating

trans mit ters with con tin u ous purge.

þNOTE: Do not turn off the purge air sup ply to use the trans mit ter as though it does not have the purge op tion; this will cause er rors.

A.Connect an accurate test DP sig nal to the MST2000, equal to the 0% minimum range value.

B.While in the PROGRAMMING MODE, step to the INPUTO parameter to display the existing value of INPUT OFFSET.

C.Press the EDIT/SAVE key once to dis play the DP read ing. Use the INCREMENT/DECREMENT keys as needed to ad just the dis play to match the test DP sig nal value.

D.Press the EDIT/SAVE key to exit the edit mode and to save the INPUT OFFSET value, (even if it was not changed).

E.Ad just the test DP sig nal to the 100% max i mum range value. Step to the INPUTG pa ram e ter to dis- play the ex ist ing value of INPUT GAIN.

F.Press the EDIT/SAVE key once to dis play the DP read ing. Use the INCREMENT/DECREMENT keys as needed to ad just the dis play to match the test DP sig nal value.

G.Press the EDIT/SAVE key to exit the edit mode and to save the INPUT GAIN value.

þNOTE: Changes to INPUTO or INPUTG will af fect both the dis play & the mA for any ap plied DP value. Ad justing OUTPTO or OUTPTG will af fect only the mA value for any ap plied DP value.

Page 34

MST2000 Multivariable SMARTFLOW ® Transmitter

Brandt Instruments, Inc.

Page 33
Image 33
Tamron MST2000 operation manual 16.2DP CALIBRATION