OPERATION MANUAL | ALARM PROGRAMMING INFORMATION |
G.Hardware Fault: Indicates hardware fault error from MST2000 internal circuitry is active.
•Bi nary value = 64.
H.Watchdog Timer Fault: Indicates watchdog timer fault error from internal microprocessor is active.
•Bi nary value = 128.
9.6 Alarm ‘ENABLE’ Word Decimal CalculationExamples
To calculate the decimal word equivalent for the ALARM ‘ENABLE’ WORD the user must determine which alarms and alarm control bits are to be enabled and then sum the binary values of each enabled bit. The decimal word equivalent is then programmed into the ALARM ‘ENABLE’ WORD using the programming menus.
A. EXAMPLE 1
The user desires to enable the following alarm/alarm control enable bits:
LCD Icon, Fail-low, RTD Fault and Under-range.
a.LCD Icon bi nary value = 2048
b.
c.RTD Fault bi nary value = 4
d.Un
•Decimalequivalent sum = 2309 (dec i mal value to pro gram into ALARM ‘EN ABLE’ WORD). B. EXAMPLE 2
The user desires to enable the following alarm/alarm control enable bits:
Digital Out1, Latched Output,
a.Dig i tal Out1 bi nary value = 8192
b.Latched Out put bi nary value = 4096
c.
d.ISO Comm er ror bi nary value = 8
e.
f.Un
•Decimalequivalent sum = 12811 (dec i mal value to pro gram into ALARM ‘EN ABLE’ WORD).
9.7Alarm ‘STATUS’ Word Decimal Decode Examples
To determine which individual alarm status bits are active, the user must take the decimal equivalent value from the ALARM ‘STATUS’ WORD register and decode it into the associated binary bit values. This is accomplished using binary division of the decimal word. The examples below show manual division. The user may also use a decimal to binary calculator to simplify this procedure.
A.Example 1
•ALARM ‘STATUS’ WORD = 37
•Using binary division, divide the decimal word by each bi nary bit value start ing with the most sig- nificant bit value (bit 8 = 128) and then each suc ces sive lower bit.
a.37 B 128 = 0 with a re main der of 37 . . . . . . . bit 8 (Watch dog timer fault) = 0
b.37 B 64 = 0 with a re main der of 37 . . . . . . . . bit 7 (Hard ware fault) = 0
c.37 B 32 = 1 with a re main der of 5 . . . . . . . . . bit 6 (ISO comm3 er ror) = 1
d.5 B 16 = 0 with a re main der of 5 . . . . . . . . . bit 5 (ISO comm2 er ror) = 0
e.5 B 8 = 0 with a re main der of 5 . . . . . . . . . . . bit 4 (ISO comm1 er ror) = 0
f.5 B 4 = 1 with a re main der of 1 . . . . . . . . . . . bit 3 (RTD fault) = 1
g.1 B 2 = 0 with a remainder of 1 . . . . . . . . . . bit 2
h.1 B 1 = 1 with a re main der of 0 . . . . . . . . . . . bit 1 (Un
•The decimal ALARM ‘STATUS’ WORD of 37 in di cates the fol low ing ac tive alarms: ISO Comm3 error, RTD fault and
B.Example 2
Brandt Instruments, Inc. | MST2000 Multivariable SMARTFLOW ® Transmitter | Page 21 |