Thermo Products CHB1-50N, CHB1-125N, CHB1-75N, CHB1-100N, CBD1-75N, CBD1-100N Troubleshooting Guide

Models: CHB1-50N CBD1-50N CBD1-125N CBD1-100N CBD1-75N CHB1-100N CHB1-75N CHB1-125N

1 57
Download 57 pages 61.05 Kb
Page 47
Image 47
TROUBLESHOOTING GUIDE

All installations and services must be performed by qualified service personnel.

TROUBLESHOOTING GUIDE

THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO CALL FOR

HEAT. THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF MALFUNCTION OR DEVIATION FROM THE NORMAL OPERATION.

TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.

TURN THERMOSTAT TO CALL FOR HEAT DOES THERMOSTAT MAKE CONTACT?

No

Yes

 

 

 

 

 

 

 

 

 

 

No

 

 

 

No

 

IS ROOM TEMPERATURE

IS ROOM

 

 

TURN T'STAT

 

 

 

BELOW THERMOSTAT

 

TEMPERATURE

 

 

 

 

 

SETTING ABOVE

SETTING?

 

ABOVE 90 DEGREES F?

 

 

 

 

 

ROOM TEMP.

 

 

 

 

 

 

 

 

Yes

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

IS THE TRANSFORMER SUPPLYING 24 VOLTS TO THE THERMOSTAT?

Yes

REPLACE

THERMOSTAT

COOL THE THERMOSTAT

No

 

ARE WIRES CONNECTED

No

 

PROPERLY?

 

Yes

 

IS INTERNAL DAMAGE

No

 

PRESENT ON THE

 

TRANSFORMER?

 

Yes

REPLACE TRANSFORMER

CORRECT WIRE CONNECTIONS

CHECK INPUT POWER, DOOR INTERLOCK, SERVICE SWITCH AND FUSES.

IS THE INDUCER

BLOWER OPERATING?

Yes

No

IS THERE 24 VOLTS ACROSS "TH" & "TR"

AT THE INTEGRATED CONTROL MODEL?

Yes

No

CHECK FOR CONTINUITY

&PROPER CONNECTIONS

41

Page 47
Image 47
Thermo Products CHB1-50N, CHB1-125N, CHB1-75N, CHB1-100N, CBD1-75N, CBD1-100N, CBD1-125N, CBD1-50N Troubleshooting Guide