Thermo Products CBD1-75N, CHB1-125N, CHB1-75N, CHB1-100N, CBD1-100N, CBD1-125N If Led Light Flashes

Models: CHB1-50N CBD1-50N CBD1-125N CBD1-100N CBD1-75N CHB1-100N CHB1-75N CHB1-125N

1 57
Download 57 pages 61.05 Kb
Page 51
Image 51
IF LED LIGHT FLASHES:

All installations and services must be performed by qualified service personnel.

Yes

Yes

IF LED LIGHT FLASHES:

 

1 FLASH, THEN PAUSE

SYSTEM LOCKOUT

2 FLASHES, THEN PAUSE

PRESSURE SWITCH STUCK CLOSED

3 FLASHES, THEN PAUSE

PRESSURE SWITCH STUCK OPEN

4 FLASHES, THEN PAUSE

OPEN LIMIT SWITCH OR ROLLOUT SWITCH

6 FLASHES, THEN PAUSE

115 VOLT AC POWER REVERSED

7 FLASHES, THEN PAUSE

LOW FLAME SENSE SIGNAL

8 FLASHES, THEN PAUSE

CHECK IGNITOR OR IMPROPER GROUNDING

CONTINUOUS FLASHING

FLAME HAS BEEN SENSED WHEN

(NO PAUSE)

NO FLAME SHOULD BE PRESENT (NO

 

CALL FOR HEAT)

THE LED WILL ALSO FLASH ONCE AT POWER-UP.

CHECK COMPLETE SYSTEM OUT.

LED LIGHT STAYS ON CONTINUOUSLY,

COMPLETE FAILURE - REPLACE

INTEGRATED CONTROL.

TROUBLESHOOTING COMPLETE.

45

Page 51
Image 51
Thermo Products CBD1-75N, CHB1-125N, CHB1-75N, CHB1-100N, CBD1-100N, CBD1-125N, CBD1-50N, CHB1-50N If Led Light Flashes