Thermo Products CHB1-50N, CHB1-125N, CHB1-75N, CHB1-100N, CBD1-75N, CBD1-100N Blower Delay Settings

Models: CHB1-50N CBD1-50N CBD1-125N CBD1-100N CBD1-75N CHB1-100N CHB1-75N CHB1-125N

1 57
Download 57 pages 61.05 Kb
Page 39
Image 39

All installations and services must be performed by qualified service personnel.

BLOWER DELAY SETTINGS

To delay fan

 

Set Switch

turn-on by:

#1

#2

15 sec.

Off

Off

30 sec.

Off

On

*45 sec.

On

Off

60 sec,

On

On

To delay fan

Set Switch

turn-off by:

#3

#4

60 sec.

On

On

90 sec.

Off

On

*120 sec.

On

Off

180 sec.

Off

Off

*Factory Settings For Optimal Performance

5. FIELD WIRING AND REPLACING WIRING

Field wiring between the furnace and devices not attached to the furnace shall conform with the temperature limitation for Type T wire [63°F rise (35°C)] when installed with the manufacturers instructions. If any of the original factory supplied furnace wiring is replaced or a separate device other than the thermostat is wired internal to the unit 105°C thermoplastic or equivalent wire must be used.