All installations and services must be performed by qualified service personnel.
BLOWER DELAY SETTINGS
To delay fan |
| Set Switch |
#1 | #2 | |
15 sec. | Off | Off |
30 sec. | Off | On |
*45 sec. | On | Off |
60 sec, | On | On |
To delay fan | Set Switch | |
#3 | #4 | |
60 sec. | On | On |
90 sec. | Off | On |
*120 sec. | On | Off |
180 sec. | Off | Off |
*Factory Settings For Optimal Performance
5. FIELD WIRING AND REPLACING WIRING
Field wiring between the furnace and devices not attached to the furnace shall conform with the temperature limitation for Type T wire [63°F rise (35°C)] when installed with the manufacturers instructions. If any of the original factory supplied furnace wiring is replaced or a separate device other than the thermostat is wired internal to the unit 105°C thermoplastic or equivalent wire must be used.
33