IV. STARTING THE UNIT

A. SEQUENCE OF OPERATIONS

AT ANY TIME THE

 

 

 

CONTINUOUS SAFE OPERATION CHECK

GAS VALVE IS

 

 

 

IF FLAME SIMULATION CONDITION

NOT ENERGIZED

 

 

PRESENT OR ROLL-OUT SWITCH OPENS, SYSTEM

 

 

ENERGIZES INDUCER FAN FOR 15 SECONDS AND CIRCULATOR BLOWER AT

START

 

 

HEATING SPEED UNTIL SITUATION CORRECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT CALLS FOR

 

 

 

 

 

HEAT, CONTACTS CLOSE

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL BOARD ENERGIZED,

 

 

 

INDUCER ENERGIZED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE SWITCH SENSES

 

PRESSURE SWITCH SENSES

 

 

NEGATIVE PRESSURE(NO DRAIN BLOCKAGE)

ADEQUATE DIFFERENTIAL PRESSURE,

 

 

CONTACTS CLOSE

 

 

CONTACTS CLOSE

 

 

 

 

(CDB1 SERIES ONLY)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START

TRIAL

FOR

IGNITION

POWER IS APPLIED TO

 

POWER INTERRUPTION

THE SILICON NITRIDE

 

SYSTEM SHUTS OFF,

IGNITOR. IGNITOR

 

RESTARTS WHEN POWER

WARM-UP IS 20 SECONDS.

 

IS RESTORED.

AFTER IGNITOR WARM-UP,

THE GAS VALVE IS

ENERGIZED TO OPEN

 

 

 

 

 

 

 

 

FLAME MUST BE DETECTED

 

IF FLAME IS NOT DETECTED, THE

 

WITHIN 4 SECONDS IF

 

GAS VALVE IS DE-ENERGIZED,

 

FLAME IS DETECTED, THE

 

THE IGNITOR IS TURNED OFF AND

 

 

DELAY-TO-FAN-ON TIME

 

THE CONTROL BOARD CONTROL GOES

 

BEGINS (45 SECONDS)

 

INTO "RETRY" SEQUENCE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

Page 40
Image 40