All installations and services must be performed by qualified service personnel.
DIAGNOSTIC FEATURES
![: Power must be disconnected before servicing.](/images/new-backgrounds/34571/3457161xi2.webp)
![The LED will also flash once at power-up.](/images/new-backgrounds/34571/3457161xi3.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi4.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi5.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi6.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi7.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi8.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi9.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi10.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi11.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi12.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi13.webp)
![Manual background](/images/new-backgrounds/34571/3457161xi14.webp)
: Power must be disconnected before servicing.
The
If the sensed failure is in the system (external to the control), the LED will flash in the following
1 flash, then pause | System lockout |
2 flashes, then pause | Pressure switch stuck closed |
3 flashes, then pause | Pressure switch stuck open |
4 flashes, then pause | Open limit switch or rollout switch |
6 flashes, then pause | 115 Volt AC power reversed |
7 flashes, then pause | Low flame sense signal |
8 flashes, then pause | Check igniter or improper grounding |
Continuous flashing | Flame has been sensed when |
(No pause) | no flame should be present |
| (No call for heat) |
The LED will also flash once at power-up.
30