3.4 Installing UPS external and battery power wiring
NOTE
The UPS cabinet is shipped with a debris shield covering the ventilation grill on top of the unit. Do not remove the debris shield until installation is complete. However, remove the shield before operating the UPS. Once the debris shield is removed, do not place objects on the ventilation grill.
NOTE
Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit holes (see Figure
NOTE
If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper. See Table
Use the procedures in the following paragraphs to connect the external and battery power wiring.
3.4.1 External power wiring installationTo install wiring to connections:
1.Remove one top screw and two bottom screws securing the UPS left front panel (see Figure
2.Route the input and output cables through either the top or bottom of the cabinet to the UPS terminals. See Figure
3.Connect phase L1, L2, and L3 (E1, E2, E3), rectifier input power wiring from the utility source to the rectifier input terminals in the UPS cabinet. See paragraph 2.2.2 on page 14 for wiring and termination requirements.
4.Connect phase L1, L2, and L3 (E6, E7, E8), and Neutral (if required) bypass input power wiring from the utility source to the bypass input terminals and neutral terminals in the UPS cabinet. See paragraph 2.2.2 on page 14 for wiring and termination requirements.
5.Connect phase L1, L2, and L3 (E9, E10, E11), and Neutral (if required) power wiring from output terminals and neutral terminals to the critical load. See paragraph 2.2.2 on page 14 for wiring and termination requirements.
6.Proceed to paragraph 3.4.2.
1027212 | UPS 225 - 275 kVA | 25 |
Revision B | User’s and Installation Guide |
|