Note Remote EPO switch rating is 24 Vdc, 1 A minimum.
Note Remote EPO
10.If you are installing multiple remote EPO switches, wire additional switches in parallel with the first remote EPO.
11.If required, install wiring from the remote EPO switch to the trip circuitry of the upstream protective devices. A
12.When all wiring is complete, reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
13.Reinstall the center front panel removed in previous steps and secure with the retained hardware.
14.Figure
Note Remote EPO switch rating is 24 Vdc, 1 A minimum.
Note Remote EPO
1027212 | UPS 225 - 275 kVA | 37 |
Revision B | User’s and Installation Guide |
|