7 Communication
This chapter describes the communication features of the Powerware 9395 225–275 kVA UPS and provides information about connecting hardware and usingTerminal mode. For terminal wiring information, see paragraph 2.2.3 on page 17 and paragraph 3.5 on page 28. For location of the customer interface panels and terminals, see Figure 3-3 on page 26 and Figure 3-7 through Figure 3-9 starting on page 30.
7.1 X-Slot cards
The Powerware 9395 UPS four X-Slot communication bays (see Figure 3-7 on page 30 for).The UPS is compatible with the following X-Slot cards (see Figure 7-1):
•Modbus card - provides direct integration of UPS information (meters and status) to a Building Management System (BMS) using the Modbus RTU protocol.
•ConnectUPS-X Web/SNMP card - provides remote monitoring through a Web browser interface, e-mail, and a network management system (NMS) using SNMP; connects to a twisted-pair Ethernet (10/100BaseT) network. It has a built-in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops.This card is provided as standard equipment with the UPS.
NOTE
The Modem card cannot be installed in X-Slot 2.•Modem card - provides “out-of-band” remote notification and monitoring using modem communication directly to cell phones and pagers.
•Relay Interface card (AS/400) - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass when interfacing with IBM® AS/400 computers, other relay connected computers, and industrial applications.
•Industrial Relay card (IRC) - indicates the operating status of the UPS system using the customer’s monitoring equipment.The IRC uses four isolated normally-open or normally- closed dry relay contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm modes can be monitored.
Figure 7-1. Optional X-Slot cards66 | UPS 225 - 275 kVA | 1027212 |
| User’s and Installation Guide | Revision B |