Function | Subfunction | Operation |
kW Demand Log |
| The kW Demand Log screen displays the individual log entries, including the |
|
| interval date and time frame, the maximum reading during the interval, the total |
|
| time over limit during the interval, an estimated number of total kWh used during |
|
| the interval, and the number of times over limit during the interval. If no events |
|
| have occurred, the screen displays LOG EMPTY. Press the LOG pushbutton on |
|
| the kW Demand Log Summary menu bar to display the kW Demand Log screen. |
|
| To scroll through the individual events, press the up or down arrow pushbuttons |
|
| on the menu bar. To return to the kW Demand Log Summary screen, press the |
|
| SUMMARY pushbutton on the menu bar. To clear the kWDemand Log, press the |
|
| RESET pushbutton on the menu bar. |
kW Demand Log | Screen 1 | The Current kW Demand Log Setup screen 1 displays the current |
Setup |
| log settings. If no log settings are configured, the screen will display kWLOG |
|
| DISABLED. Press the SETUP pushbutton on the kW Demand Log Summary |
|
| menu bar to display the Current kW Demand Log Setup screen 1. To return to |
|
| the kWDemand Log Summary screen, press the return arrow pushbutton on the |
|
| menu bar. |
| Screen 2 | The Current kW Demand Log Setup screen can be used to set up or change the |
|
| time interval and maximum level log settings. Press the CHANGE pushbutton on |
|
| the Current kW Demand Log Setup menu bar to display the Current kW Demand |
|
| Log Setup screen 2. Use the up or down arrow pushbuttons to highlight the setup |
|
| function screen desired, then press the SELECT pushbutton to display the func- |
|
| tion screen. To return to the Current kW Demand Log Setup screen 1, press the |
|
| return pushbutton on the menu bar. |
| Time Interval Moni- | The Time Interval Monitored Setup screen allows the time duration of the event |
| tored Setup | being monitored to be changed. Select TIME INTERVAL MONITORED from |
|
| the Current kW Demand Log Setup screen 2 menu to display the Time Interval |
|
| Monitored Setup screen. Use the left or right arrow pushbuttons to select the |
|
| character position. Use the up or down arrow pushbuttons to change the char- |
|
| acter value. Once the new value is entered, press the DONE pushbutton. The |
|
| Time Interval Monitored Setup Save screen is displayed. |
| Time Interval Moni- | The Time Interval Monitored Setup Save screen lets you save the new time |
| tored Save | interval, retry another time interval, or abort the change. Press SAVE, RETRY, or |
|
| ABORT. If SAVE or ABORT is pressed, the action is completed, and the Current |
|
| kW Demand Log Setup screen 2 displays. If RETRY is pressed, the Time Interval |
|
| Monitored Setup screen is redisplayed. |
| Maximum Level | The Maximum Level (kW) Setup screen allows the kW limit of the event being |
| (kW) Setup | monitored to be changed. Select MAXIMUM LEVEL (kW) from the Current kW |
|
| Demand Log Setup screen 2 menu to display the Maximum Level (kW) Setup |
|
| screen. Use the left or right arrow pushbuttons to select the character position. |
|
| Use the up or down arrow pushbuttons to change the character value. Once |
|
| the new value is entered, press the DONE pushbutton. The Maximum Level (kW) |
|
| Setup Save screen is displayed. |
| Maximum Level | The Maximum Level (kW) Setup Save screen lets you save the new kW limit, |
| (kW) Save | retry another kW limit, or abort the change. Press SAVE, RETRY, or ABORT. If |
|
| SAVE or ABORT is pressed, the action is completed, and the Current kW Demand |
|
| Log Setup screen 2 displays. If RETRY is pressed, the Maximum Level (kW) Setup |
|
| screen is redisplayed. |
Maximum Current |
| The maximum current log collects information on events where the unit load |
Log Summary |
| exceeds a |
|
| can choose a time period up to 9999 minutes and a load limit up to 100%. The |
|
| user can also select whether the limit defined is a |
|
| individual phase currents or is a limit defined for each phase individually. In the |
|
| first case an event is logged if the average across the phases exceeds the de- |
|
| fined limit within a given time period and in the second case an event is logged |
|
| if any individual phase exceeds the defined limit within a given time period. The |
|
| Maximum Current Log Summary screen displays the number of times the limit |
|
| has been exceeded, the date of the last log reset, the maximum percent of full |
|
| load, and the total time over the limit. It also displays the average percent load |
|
| over the limit. This measurement differs, depending on whether a |
|
| average or an individual phase measurement is selected. Press the METERS |
|
| pushbutton on the main menu bar to display the Unit Meter screens. Scroll |
|
| through the meter screens using the up or down arrow pushbuttons on the menu |
|
| bar until the Maximum Current Log Summary screen is displayed. |
1027212 | UPS 225 - 275 kVA | 53 |
Revision B | User’s and Installation Guide |
|