Toro TWRS manual Wiring Procedure II no sensor feature, Attach the White wire to this terminal

Models: TWRS

1 28
Download 28 pages 35.58 Kb
Page 9
Image 9
Wiring Procedure II (no sensor feature)

For a normally-opensensor, attach the Yellow wire to the remaining sensor terminal. Tape back the Brown wire. See Figure 3.

4.Attach the Red wires to the 24 Vac terminals. Important Most controllers with sensor connections also provide a control switch to bypass sensor operation if necessary. Check the switch setting to make sure it is not in the Bypass or Active position.

Wiring Procedure II (no sensor feature)

1.Locate the valve common wire terminal, generally labeled “C” or “COM”, and remove all common wires for valves, pump relay, etc.

2.Attach the White wire to this terminal.

3.Splice the Brown wire to the common wires and insulate the connection using a wire nut or electrical tape. Tape back the Yellow wire. See Figure 4.

4. Attach the Red wires to the 24 Vac terminals.

Figure 3 - Normally-open Sensor

 

 

 

 

 

 

PUMP/

 

SENSOR

24 VAC

 

1

2

3

4

MV

COM

 

 

 

 

 

 

 

Yellow

White

Red

Red

Red

 

 

 

 

 

 

 

 

 

 

To Valves

 

 

 

 

 

 

 

Red

 

 

 

 

 

 

 

 

 

 

White

 

 

 

 

 

 

 

 

 

 

Yellow

 

 

 

 

 

 

 

 

 

X

Brown

Figure 4 - Splice Valve Common

 

 

1

2

3

4

PUMP/MV

COM

24 VAC

 

 

 

 

 

 

White

Red

Red

 

 

 

 

 

 

 

 

 

Red

 

 

 

 

 

 

 

 

Red

Common

 

 

 

 

 

White

 

 

 

 

 

Brown

To Valves and

 

 

 

X

Yellow

Pump/MV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Page 9
Image 9
Toro TWRS manual Wiring Procedure II no sensor feature, Attach the White wire to this terminal