TOSHIBA

Fixed Frequency Mode

The 1700 Series Rackmount UPS has the option of operating in a fixed frequency mode. Normally the UPS operates in the frequency auto-detect mode. If a specific output frequency is required (i.e. 50Hz or 60Hz) the UPS can be set at the factory to supply the desired frequency regardless of the input frequency (input frequency must be within allowable limits, see Specifications on page 29). For a unit already in use the output frequency can be set through software. For instructions on setting the output frequency through software please contact Toshiba at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com. It is important to note that when the

UPS is operating with a fixed output frequency, output is disabled in bypass.

Adding an Additional Battery Module

Note: Only one additional battery module may be added to the standard unit. Figure 4 shows the standard unit with one additional battery module added. To install an additional battery module follow these steps:

1)Make room in the rack for the additional battery module to be placed below the other modules. Secure the new battery module in the rack.

2)Plug the new battery module output power cord into the battery input plug on the battery module.

.

Figure 4

Expansion Battery Module

19

Page 19
Image 19
Toshiba 1700 user manual Fixed Frequency Mode