Appendix E: Bypass Undervoltage / Overvoltage

When the 1700 Series Rackmount UPS is in bypass mode the undervoltage and overvoltage limits are restricted to +/-10% of the rated input voltage. If the input voltage is outside of this voltage window the UPS output will be turned off. There is a 5% hysteresis associated with both the upper and lower limits. This means that once output has been turned off the input voltage will have to be within ±5% of the rated input voltage before the startup sequence will reinitialize. (To start the UPS when the input power is outside of the allowable range see the section entitled “Starting on DC Power”, page 12.)

When the UPS is started, if the RUN/STOP switch is in the STOP (bypass) position the unit will start in the on-line mode for 1 second before switching to bypass mode. If the input voltage is out of range the UPS will turn off the output after 1 second rather than switching to bypass.