Appendix B: Fan Speed Control

The fans in the 1700 Series will operate at any of four different speeds depending on the environment and system conditions. In the first stage the fans are off. As the load and or the temperature increase the fans will subsequently go to low, medium or high speed as required.

The temperature reference given on the graph above refers to the temperature inside the UPS. There will typically be a 5°C difference between the internal and external temperature. The 10% hysteresis shown is to ensure that the unit will not oscillate between fan speeds. When the output power reaches a level that requires the fan speed to increase the load will have to be reduced 10% below that level before the fan speed will return to the lower speed.