23

Warnings (cont’d)

Warning

Display State

LED State

Alarm State

Description and Resolution

Input

 

Warning/Fault ... Flash

Alarm will

The input frequency is outside

Frequency

 

60% .................. Flash

sound for

specified limits. If the unit was

 

online when the warning occurred

Regulation

 

 

3, 1/2-

 

 

it will transfer to battery backup.

(see note 1)

 

 

second

After the backup the output will

 

 

 

 

 

beeps at

shutdown. If the unit was in

 

 

 

 

 

10-second

bypass the output will be turned

 

 

 

 

 

off. The unit will return to normal

 

 

 

 

 

intervals.

 

 

 

 

 

operation if input frequency

 

 

 

 

 

 

returns to within specified limits.

 

 

 

 

 

Output

 

Warning/Fault ... Flash

Alarm will

The connected load exceeds

Overload

 

150% ................ Flash

sound for

the UPS power rating.

 

 

 

 

 

1-second

Reduce the load attached to

 

 

 

 

 

the UPS. The unit will

 

 

 

 

 

at 15-

 

 

 

 

 

automatically return to normal

 

 

 

 

 

second

 

 

 

 

 

operation.

 

 

 

 

 

intervals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

= Flashing LED

 

= LED lit continuously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1: If any of these faults occur while the UPS is in online mode it will immediately transfer to backup mode. In this case the percentage LED’s will be used to show the battery power status. To identify the fault that has occurred listen to the number of consecutive beeps. One beep indicates an input undervoltage, two beeps means input overvoltage, three beeps is a frequency problem.

Note 2: Once the batteries are exhausted the unit will either shutdown the output, or switch to bypass according the selections set by the user (see the section entitled “Programming Mode” part B on page 18).