21

Warnings

Warning

Display State

LED State

Alarm State

Description and Resolution

Low Battery

Warning/Fault ... Flash

Alarm will

The batteries have less than

 

Backup.............. Flash

sound for

30% power remaining. The

 

 

1-second

warning will continue until either

 

 

the batteries become completely

 

 

at 5-

 

 

exhausted or AC input power is

 

 

second

 

 

restored.

 

 

intervals.

 

 

 

 

 

 

 

Current

Warning/Fault ... Flash

Alarm will

An output current limit warning

is typically a sign of

Limit (Over

80% .................. Flash

sound for

misapplication. The load may

Current)

 

1/2-

 

not be appropriate for UPS

 

 

second at

 

 

support. For further explanation

 

 

1-second

contact your Toshiba UPS

 

 

intervals.

service representative at 1-877-

 

 

 

867-8773(outside the U.S.

 

 

 

call 713-466-0277).

Ambient

Warning/Fault ... Flash

Alarm will

The temperature of the UPS

Over Heat

100% ................ Flash

sound for

operating environment is too

 

 

1-second

high. Causes of this condition

 

 

at 15-

include allowing the room

 

 

temperature to exceed 104°F

 

 

second

 

 

(40°C), a blocked vent or direct

 

 

intervals.

 

 

sunlight on the unit. The unit will

 

 

 

 

 

 

transfer to bypass until the

 

 

 

temperature is reduced.