LF410/LF600 LF410/LF602

Wiring Precautions

(1)Explosion proof type flowmeters are not provided cable glands.

Refer to the part Cable connection port at detector and converter.

(2)Connect the grounding wire (IV wire 5.5mm² or more) to a good earth ground (100Ω or less ground resistance). Make the wire as short as possible. Do not use a common ground shared with other equipment where earth current may flow. An independent earth ground is recommended.

(3)The allowable cable lengths between the detector and converter for the separate type flowmeter depend on the electrical conductivity of the object fluid. See Figure 12 below.

(4)DO1, DO2 (opt.), and DI (opt.) use the same common terminal (COM). This COM can not connect to other equipments which have their own ground terminal.

(Power supply for connecting to DI or DO, etc…) Need to wire separately.

Wiring Precautions (PROFIBUS)

(1)For wiring path, avoid places near electrical equipment that may cause electromagnetic induction or electrostatic induction interference (such as a motor, transformer and wireless transmitter).

(2)Use a PROFIBUS-PA cable for signal cable. In addition, make sure to use a shielded cable to improve noise resistance. Furthermore, installation of signal cable in metal conduit is recommended.

(3)General PROFIBUS-PA cables are designed for indoor use where cables are not exposed to humidity, rain, etc. When you install cables, make sure to check the operating conditions such as the operating temperature range of the cable by contacting its manufacturer.

(4)When you carry out cable end treatment of PROFIBUS-PA cable, use a dedicated cable stripper etc. so that the core wire of the cable will not be nicked or damaged. In addition, for cables, be careful of allowable maximum bend diameter etc. (Basically, do not install cables in a way cables are twisted or bent.).

(5)Consider installing a PROFIBUS-PA arrester in the communication path of PROFBUS-PA so that the electromagnetic flowmeter will not be affected by lightning etc.

(6)The electromagnetic flowmeter is not equipped with terminating resistors.Use the terminating resistor unit for PROFIBUS-PA or junction box, if necessary.

(7)Only one PROFIBUS-PA cable goes through a cable gland of the Electromagnetic Flowmeter. Please use the junction box at system configuration.

 

300

 

 

 

 

200

 

 

 

(m)

100

 

 

 

50

 

 

 

cable length

 

 

 

30

 

 

 

10

 

 

 

Allowable

5

 

 

 

3

 

 

 

 

3

5

10 20 30

50 100 200

 

 

Conductivity (μS/cm)

Figure 12. Electrical Conductivity and

Cable Length

10

Page 10
Image 10