3 SELECTION OF INSTALLATION
<Obstacle also at the upper side>
1000 | 1000 moreor |
or more |
|
Obstacles at both front and rear sides
Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit.
<Standard installation>
1. Single unit installation
1000150 or more or more
2. Serial installation of two or more units
|
| 200 or more |
300 | 300 | 1000 moreor |
or more | or more |
|
Serial installation at front and rear sides
Open the upper side and both right and left sides. The height of obstacle at both front and rear sides should be lower than the height of the outdoor unit.
<Standard installation>
1000 | 300 | 1500 | 2000 | 200 |
or more | or more | or more | or more | or more |
Installation of Outdoor Unit
•Before installation, check strength and horizontality of the base so that abnormal sound does not generate.
•According to the following base diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
<SM560AT-E>
| 90 | 600 | 90 |
|
| 115 |
|
330 | 310 | 76 |
|
Ø28 Drain hole
<SM800AT-E, SP560AT-E, SP800AT-E>
|
| 150 |
| 600 | 150 |
|
|
|
|
| 430 |
|
|
| Drain hole | 40 | |
|
|
|
|
| |
400 | 365 | Knockout hole | Drain nipple mounting hole | ||
|
|
|
|
Set the out margin of the anchor bolt to 15mm or less.
15 or less
•In case of draining through the drain hose, attach the following drain nipple and the waterproof rubber cap, and use the drain hose (Inner diam.: 16mm) sold on the market. And also seal the screws securely with silicone material, etc. so that water does not drop down. Some conditions may cause dewing or drip- ping of water.
Drain nipple | Waterproof rubber cap |
40