3 SELECTION OF INSTALLATION
<Obstacle also at the upper side>
1000 | 1000 moreor |
or more |
|
Obstacles at both front and rear sides
Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit.
<Standard installation>
1. Single unit installation
1000150 or more or more
2. Serial installation of two or more units
|
| 200 or more |
300 | 300 | 1000 moreor |
or more | or more |
|
Installation of Outdoor Unit
•Before installation, check strength and horizontality of the base so that abnormal sound does not generate.
•According to the following base diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
|
| 150 |
| 600 | 150 |
|
|
|
|
| 430 |
|
|
| Drain hole | 40 | |
|
|
|
|
| |
400 | 365 | Knockout hole | Drain nipple mounting hole | ||
|
|
|
|
Set the out margin of the anchor bolt to 15mm or less.
15 or less
•In case of drainning through the drain hose, attach the following drain nipple and the waterproof rubber cap, and use the drain hose (Inner diam.: 16mm) sold on the market. And also seal the screws securely with silicone material, etc. so that water does not drop down. Some conditions may cause dewing or drip- ping of water.
Serial installation at front and rear sides
Open the upper side and both right and left sides. The height of obstacle at both front and rear sides should be lower than the height of the outdoor unit.
<Standard installation>
1000 | 300 | 1500 | 2000 | 200 |
or more | or more | or more | or more | or more |
Drain nipple | Waterproof rubber cap |
Knockout hole
Open
Waterproof rubber cap
Drain nipple
•When there is a possibility of freezing of drain at the cold district or a snowfall area, be careful for drainage ability of drain. The drainage ability increases when a knockout hole on the base plate is opened. (Open the knockout hole to outside using a screwdriver, etc.)
54