3 SELECTION OF INSTALLATION
CAUTION
<SP560AT-E, SP800AT-E only>
When using an air conditioner under low outside temperature condition (Outside
<Example>
<SP560AT-E>
Length of refrigerant pipe |
| |
connected to | Item | |
indoor/outdoor unit |
| |
|
| |
20m or shorter | Addition of refrigerant is | |
unnecessary at the local site. | ||
| ||
|
| |
*21m to 50m | <Addition of refrigerant> | |
Add 20g of refrigerant for every | ||
| 1m of pipe which exceeds 20m. | |
|
|
Suction hood (Rear side)
Suction hood (Side)
Discharge hood
Discharge
* Caution at addition of refrigerant |
When the total length of refrigerant pipe exceeds |
20m, add 20g/m of refrigerant and the maximum total |
length of pipe is 50m. |
(Max. amount of additional refrigerant is 600g.) |
Discharge guide | Fin |
Fin |
|
Suction | Suction |
|
Before installation
Be careful to the following items before installation.
Length of refrigerant pipe
Length of refrigerant pipe |
| |
connected to | Item | |
indoor/outdoor unit |
| |
|
| |
20m or shorter | Addition of refrigerant is | |
unnecessary at the local site. | ||
| ||
|
| |
*21m to 30m | <Addition of refrigerant> | |
Add 20g of refrigerant for every | ||
| 1m of pipe which exceeds 20m. | |
|
|
*Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds 20m, add 20g/m of refrigerant and the maximum total length of pipe is 30m.
(Max. amount of additional refrigerant is 200g.)
Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.
Charge the refrigerant accurately. Overcharge may |
cause a serious trouble of compressor. |
<SP800AT-E>
Length of refrigerant pipe |
| |
connected to | Item | |
indoor/outdoor unit |
| |
30m or shorter | Addition of refrigerant is | |
unnecessary at the local site. | ||
| ||
|
| |
*31m to 50m | <Addition of refrigerant> | |
Add 40g of refrigerant for every | ||
| 1m of pipe which exceeds 30m. |
*Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds 30m, add 40g/m of refrigerant and the maximum total length of pipe is 50m.
(Max. amount of additional refrigerant is 800g.)
Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.
Air purge
•For air purge, use a vacuum pump.
•Do not use refrigerant charged in the outdoor unit for air purge. (The refrigerant for air purge is not con- tained in the outdoor unit.)
<SM800AT-E>
Length of refrigerant pipe |
| |
connected to | Item | |
indoor/outdoor unit |
| |
|
| |
20m or shorter | Addition of refrigerant is | |
unnecessary at the local site. | ||
| ||
|
| |
*21m to 50m | <Addition of refrigerant> | |
Add 40g of refrigerant for every | ||
| 1m of pipe which exceeds 20m. | |
|
|
*Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds 20m, add 40g/m of refrigerant and the maximum total length of pipe is 50m.
(Max. amount of additional refrigerant is 1200g.)
Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.
Electrical cabling
•Be sure to fix the power cables and indoor/outdoor connecting cables with clamps so that they do not contact with the cabinet, etc.