6 ELECTRICAL WORK
For the air conditioner that has no power cable, connect a power cable as mentioned below.
|
|
| ||
Model RAV- | ||||
|
|
| ||
|
|
| ||
Power supply | 220 – 240 V | |||
Single phase 50 Hz | ||||
| ||||
|
|
| ||
Maximum running current | 12A |
| 15A | |
|
|
|
| |
Installation fuse rating | 25 A (D type | ) | ||
|
| |||
Power cable | H07 | |||
(2.5 mm2 or more) | ||||
|
|
|
|
CAUTION
•Wrong wiring may cause a burnout to some electrical parts.
•Be sure to use the cord clamps attached to the product.
•Do not damage or scratch the conductive core and inner insulator of power and
•Be sure to comply with local regulations of the cable from outdoor unit to indoor unit.
(wire size and cabling method etc.)
•Use the power and
<SM560AT-E>
How to remove the valve cover
1.Remove screws of the valve cover.
2.Pull the valve cover downward to remove it.
Valve cover
Piping cover
Cord clamp
Indoor/outdoor connecting cables
Power cable
How to wire
1.Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit.
H07
2.When connecting the connecting cable to the outdoor unit terminal, prevent water coming in the outdoor unit.
3.Insulate the unsheathed cords (conductors) with electrical insulation tape. Process them so that they do not touch any electrical or metal parts.
4.For inter connecting cable, do not use a wire jointed to another on the way.
Use wires long enough to cover the entire length.
Terminal block
1 2 3 L N
Screw
Connecting Power cable cable
Stripping length power cord and connecting cable
L N | 10 | 10 | 1 2 3 |
10 |
|
| 10 |
40 | 40 |
30 | 30 |
Earth line | Earth line | (mm) |
|
| |
Power cable | Connecting |
|
| cable |
|
CAUTION
•The installation fuse (25A D type ) must be used for the power supply line of this air conditioner.
•Incorrect/incomplete wiring might cause an electrical fire or smoke.
•Prepare the exclusive power supply for the air conditioner.
•This product can be connected to the mains. Connection to the fixed wiring :
A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.
47