Toshiba RAV-SP1100UT-E, RAV-SP560AT-E Accessory And Refrigerant, Accessory and Installation Parts

Models: RAV-SP1100UT-E RAV-SP800AT-E RAV-SP1100AT-E RAV-SP1400UT-E RAV-SP560AT-E

1 31
Download 31 pages 33.89 Kb
Page 19
Image 19
Manual background

When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.

Install the air conditioner securely in a location where the base can sustain the weight adequately.

Perform the specified installation work to guard against an earthquake.

If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.

If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.

After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.

Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.

An insufficient power supply capacity or inappropriate installation may cause fire.

Use the specified cables for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from affecting the terminals.

Be sure to provide grounding.

Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.

Conform to the regulations of the local electric company when wiring the power supply. Inappropriate grounding may cause electric shock.

Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks, and stays around the unit, a fire may occur.

Required tools for installation work

R410A (Special requirement)

1)Philips screw driver

2)Hole core drill (65 mm)

3)Spanner

4)Pipe cutter

5)Knife

6)Reamer

7)Gas leak detector

8)Tape measure

9)Thermometer

10)Mega-tester

11)Electro circuit tester

12)Hexagonal wrench

13)Flare tool

14)Pipe bender

15)Level vial

16)Metal saw

17)Gauge manifold

(Charge hose : R410A special requirement)

18)Vacuum pump

(Charge hose : R410A special requirement)

19)Torque wrench

1/4 (17 mm) 16 N•m (1.6 kgf•m) 3/8 (22 mm) 42 N•m (4.2 kgf•m) 1/2 (26 mm) 55 N•m (5.5 kgf•m)

5/8 (15.9 mm) 120 N•m (12.0 kgf•m)

20)Copper pipe gauge adjusting projection margin

21)Vacuum pump adapter

SP1100AT-E

SP1400AT-E

RAV-

RAV-

 

 

2 ACCESSORY AND REFRIGERANT

Accessory and Installation Parts

1

3

Outdoor unit

 

Installation manual x 1

Protective bush

Drain nipple

 

2

4

 

Guard material for

Waterproof rubber cap

passage part

Refrigerant Piping

Piping kit used for the conventional refrigerant cannot be used.

Use copper pipe with 0.8 mm or more thickness for Ø9.5.

Use copper pipe with 1.0 mm or more thickness for Ø15.9.

Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it.

51

Page 19
Image 19
Toshiba RAV-SP1100UT-E, RAV-SP560AT-E Accessory And Refrigerant, Accessory and Installation Parts, Refrigerant Piping