Toshiba RAV-SP1400UT-E, RAV-SP560AT-E Final Installation Checks, Check and Test Operation

Models: RAV-SP1100UT-E RAV-SP800AT-E RAV-SP1100AT-E RAV-SP1400UT-E RAV-SP560AT-E

1 31
Download 31 pages 33.89 Kb
Page 16
Image 16
7 FINAL INSTALLATION CHECKS

7 FINAL INSTALLATION CHECKS

Check and Test Operation

For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.).

*The conventional leak detector for HCFC refrigerant (R22, etc.) cannot be used because its sensitivity for HFC refrigerant lowers to approx. 1/40.

Pressure of R410A is approx. 1.6 times higher than that of R22.

If installation work is incompletely finished, a gas leakage may occur when pressure rises during operation.

Therefore, be sure to test the piping connections for leakage.

Check gas leakage at the flare nut connections, valve stem cap connections and service port cap fittings with a leak detector or soap water.

Valve cover

Piping cover

Check points of outdoor unit

Flare nut connections (Indoor unit)

CAUTION

When the remote controller is used for the first time, it accepts an operation approx. 5 minutes after the power supply has been turned on.

It is not a trouble, but is because the setup of the remote controller is being checked.

For the second power-ON time and after, approx. 1 minute is required to start the operation by the remote controller.

Useful Functions

(SM800AT-E, SP560AT-E, SP800AT-E)

Self-Diagnosis by LED Indication

In addition to the code checking by remote controller of the indoor unit, troubles of the outdoor unit can be diag- nosed by LED indications on the cycle control P.C. board of the outdoor unit. Utilize them for various checks. For the check by remote controller of the indoor unit, refer to the Installation Manual of the indoor unit.

Before a check, confirm each bit of the DIP switch is set to OFF position.

LED indication and code checking

 

Cycle control P.C. board

 

LED indication

 

LED indication

Cause

 

D800

D801

D802

D803

 

 

¡

 

l

l

l

Heat exchanger sensor (TE) error

 

 

 

 

 

 

 

 

l

 

l

¡

l

Suction sensor (TS) error

 

 

 

 

 

 

 

 

¡

 

¡

l

l

Discharge sensor (TD) error

 

 

 

 

 

 

 

 

l

 

¡

l

¡

High-pressure protection error

D800 ¡ : Red

 

 

 

 

 

 

l

 

¡

l

l

Outdoor temperature sensor (TO) error

D801 ¡ : Yellow

 

 

 

 

 

 

¡

 

¡

¡

l

DC outside fan error

D802 ¡ : Yellow

 

 

 

 

 

 

 

¡

 

l

l

¡

Communication error between IPDU (Abnormal stop)

D803 ¡ : Yellow

 

 

 

 

 

 

 

l

 

¡

l

¡

High-pressure release operation

 

 

 

 

 

 

 

 

 

¥ : Rapid flash

l

 

¡

¡

l

Discharge temp. error

 

 

 

 

 

 

l : Go off

¡

 

¡

l

¡

EEPROM error

¡ : Go on

l

 

l

¡

¡

Communication error between IPDU (No abnormal stop)

 

 

 

 

 

 

 

 

¥

 

l

l

l

G-Tr short-circuit protection

 

 

 

 

 

 

 

 

l

 

¥

l

l

Detect circuit error

 

 

 

 

 

 

 

 

¥

 

¥

l

l

Current sensor error

 

 

 

 

 

 

 

 

l

 

l

¥

l

Comp. lock error

 

 

 

 

 

 

 

 

¥

 

l

¥

l

Comp. break down

 

 

 

 

 

 

 

48

Page 16
Image 16