TOSLINE-S20 Active Star Coupler (ASC25) Instruction Manual

6F3B0360

6.4Function setting switch

Arrangement and names of function setting switches are given below.

Figure 6.3

Name

Description

Use

TX1

Setting the function of preventive

Preventive measures to single-wire

measures to single-wire breaking

breaking

 

TX10

Setting the function of preventive

Preventive measures to single-wire

measures to single-wire breaking

breaking

 

OPTST

Setting the function for determining

Optical power determination

optical power

 

 

 

A.TST

Setting the function for automatic

Quality assurance test

testing

 

 

 

Table 6.2

(1)Setting switch "TX1"

Turn the switch to "ON" position, and the function of preventive measures to single-wire

breaking of CH1 is actuated. In the case that, when the function is in "ON" mode, the RX signal of CH1 cannot be detected during a period of about 400 ms, the transmission of TX signal from CH1 is stopped.

On the port which entered the stop transmission, when the switch is turned to "OFF" position after the circuit operation is resumed, the transmission is reactivated on receiving signals from other port. When the switch is turned to "ON" position again, the function is also reactivated.

When the function is in "OFF" mode, TX continues to transmit signals even if RX signal cannot be detected.

(2)Setting switch "TX10"

Turn the switch to "ON" position, and the function of preventive measures to single-wire

breaking of CH10 is actuated. In the case that, when the function is in "ON" mode, the RX signal of CH10 cannot be detected during a period of about 400 ms, the transmission of TX signal from CH10 is stopped.

TOSLINE S20

15

Page 16
Image 16
Toshiba S20 instruction manual Function setting switch, TX1