(2)Functional specifications
The functional specifications of the Active Star Coupler are listed below.
Item |
|
|
| Description | |
|
|
|
|
| |
Number of connectable | Max. 10 |
|
|
| |
stations |
|
|
|
| |
| for FC Type | Silica glass optical fiber cable (JIS C6820) | |||
Applied optical fiber | connector | GI 50/125 μm (core dia./clad dia.) | |||
for F07 Type | |||||
| |||||
| connector | SI Model 200/230μm (core dia./clad dia.) | |||
| Station to Star Coupler | : Max. 1 km | |||
Transmission distance | Star Coupler to Star Coupler : Max. 1 km | ||||
| Total system |
|
| : Max. 10 km | |
Number of | Max. 9 |
|
|
| |
connection of Star |
|
|
|
| |
Couplers |
|
|
|
| |
Connectable apparatus | |||||
| "ON" during normal operation | ||||
HEALTHY contact (Relay | Contact rating |
|
|
| |
Voltage: 250 V AC | Current: max. 1 A | ||||
contact) | Voltage: 24 V DC | Current: max. 1 A | |||
| |||||
| Voltage: 5 V AC/DC | Current: min. 10 mA |
Table 5.2
12 | ASC25 Instruction Manual |